4. Service procedures

(4) [Alarm "P22"]

Outdoor unit fan motor drive circuit trouble

Are connectors CN003 and CN004 connected correctly to the outdoor unit control PCB?

Yes

Disconnect connectors CN003 and CN004 from outdoor unit control PCB, and rotate fan by hand. Does it rotate easily?

Yes

No

No

Correct the connector

connections.

Outdoor unit fan motor coil resistance is

OK if it is as shown below.

* Disconnect connector CN004 and

No

measure on the plug side.

 

(1)Red – white: 30 – 40

(2)White – black: 30 – 40

(3)Black – red: 30 – 40

Yes

Motor position detection circuit resis- tance is OK if it is as shown below.

* Disconnect connector CN003 and measure

No

on the plug side.

(1)Grey – yellow: 100 kor more, or (open)

(2)Grey – blue: 100 kor more, or (open)

(3)Grey – orange: 100 kor more, or (open)

Yes

 

 

Fan motor is OK; outdoor unit

Fan motor trouble

4

Replace.

control PCB has failed.

 

 

Replace.

 

 

Note:

 

 

In the case of a GND circuit failure inside the motor, the results

 

of the above check may be OK.

 

 

If operation is not OK after the outdoor unit control PCB has

 

been replaced, then replace the outdoor unit fan motor.

 

 

 

SM831148

 

IV-11

 

Page 157
Image 157
Sanyo XH4272R / C4272R, UH2672R, XH2672R, UH3672R / CH3672R, XH4272R / CH4272R, XH3672R / C3672R, TH3672R Alarm P22