Sanyo KH3072R / CH3072R, UH2672R Outdoor Unit, Installation space, Installation requirements

Models: KH3072R / C3072R C4272R UH2672R / CH2672R UH2672R KH3672R / CH3672R TH2672R / CH2672R XH2672R / CH2672R UH3672R XH2672R / C2672R UH2672R / C2672R KHH2672R / CH2672R CH4272R TH3672R / CH3672R TH2672R / C2672R XH4272R / C4272R TH2672R THH2672R / CH2672R XH3672R / C3672R UH3672R / CH3672R XH2672R KH3672R / C3672R KH2672R / C2672R TH3672R / C3672R TH4272R / C4272R XH4272R / CH4272R KH2672R / CH2672R TH3672R TH4272R / CH4272R KH3072R / CH3072R THH3672R / CH3672R UH3672R / C3672R XH3672R / CH3672R XH3672R

1 180
Download 180 pages 17.39 Kb
Page 93
Image 93

1. Specifications

Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 1-1)

damp, humid or uneven locations

DO:

choose a place as cool as possible.

choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F constantly.

allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 1-2)

use lug bolts or equal to bolt down unit, reducing vibration and noise.

if cooling operation is to be used when the outdoor air temperature is 23°F or below, install a duct on the outdoor unit.

Installation space

Distance between obstructions and the unit air inlet and outlet must be as shown below.

*3

Inlet side C

More than 25/64"

More than 25/64"

*2 *4

Outlet side

More than

3.3ft.

*1

Exhaust fan

Hot air

Heat source

Out- door unit

Fig. 1-1

(Obstruction above unit)

Air direction chamber

(field supply)

 

B

 

A

*1

Inlet side

More than 8"

 

(Obstruction on

 

inlet side)

(Ground)

1

Fig. 1-2

Fig. 1-3

CAUTION

Concerning inlet-side distance “C” (Fig. 1-2)

The minimum for distance “C” is 6" if there are no obstructions on the outlet side (wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance “C” is 8".

If the unit is installed with the outlet side facing wall *1, then there must be no obstruc- tions on 2 of the remaining 3 sides: *2, *3, *4.

If wall *1 is on the outlet side (Fig. 1-2), or if obstructions are present on all 3 sides *2, *3, and *4 (Fig. 1-2), then the minimum distance for “A” and “B” is 80" (Fig. 1-3). Even if there is no wall on the outlet side, a minimum of 3.3 ft. is required.

Installation requirements

provide a solid base (concrete block, 4" × 16" beams or equal), a minimum of 6" above ground level to reduce humidity and protect the unit gainst possible water damage and decreased service life. (Fig. 1-4)

use lug bolts or equal to bolt down unit, reducing vibration and noise.

Anchor bolts (4 pieces)

Fig. 1-4

SM831148

I-89

Page 93
Image 93
Sanyo KH3072R / CH3072R, XH4272R / C4272R, UH2672R, XH2672R Outdoor Unit, Installation space, Installation requirements