4. Service procedures

(2) [Alarm “P26”]

IGBT short-circuit protection on inverter control (IPDU) PCB

HIC PCB trouble)

 

Is power OK?

No

 

Correct power line.

 

 

Yes

 

 

 

Are

 

 

 

circuit wiring,

 

 

 

connector

No

 

Correct.

connections, and

 

 

reactor

 

 

 

connections

 

 

 

OK?

 

 

 

Yes

 

 

 

Has filter PCB

No

 

 

RY001 or RY002

 

 

 

 

 

relay activated?

 

 

 

Yes

Has filter PCB

Yes

Replace filter PCB.

 

AC fuse blown?

 

 

 

 

Disconnect

No

 

 

U.V.W. output

No

 

 

terminal on HIC PCB and

 

Replace HIC PCB.

 

 

start operation.

 

 

 

 

 

Does alarm

 

 

 

“P26”

 

 

 

occur?

 

 

 

Yes

 

 

 

Is

compressor OK? No (Check for layer

short circuit.)

Yes

Is

resistance between

each terminal on No

HIC PCB OK? (See following page.)

Yes

Replace outdoor unit control PCB.

Check HIC PCB. Replace if PCB has failed.

Replace compressor.

SM831148

IV-9

Page 155