5. Outdoor unit maintenance remote control

List of Item Codes

 

 

 

 

 

 

 

 

 

 

 

Item code

 

 

 

Parameter

 

 

 

 

 

 

 

01

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

02

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

03

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

04

Snowfall sensor operation

 

0

= No sensor, control performed

 

 

 

 

1

= No sensor, control not performed

 

 

 

 

2

= Sensor present, control performed

 

 

 

 

3

= Sensor present, control not performed

 

 

 

 

 

 

 

05

Outdoor fan quiet mode

 

Do not set

 

 

 

 

 

 

 

 

06

Defrost fan speed selection

 

Do not set

 

 

 

 

 

 

 

 

 

07

Ignore capacity

 

0

= Disabled

1 = Ignores capacity ratio

 

 

 

 

 

 

 

08

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

09

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

0A

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

0b

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

 

0C

Forced operation of

 

0

= Disabled

 

 

 

indoor unit drain pump

 

1

= During cooling only, 2 hours stopped + 20 minutes operating

 

 

 

 

(regardless of whether the unit is running or stopped)

 

 

 

 

2

= During cooling only, 4 hours stopped + 20 minutes operating

 

 

 

 

(regardless of whether the unit is running or stopped)

 

 

 

 

3

= At all times, 4 hours stopped + 20 minutes operating

 

 

 

 

4

= At all times, 2 hours stopped + 20 minutes operating

 

 

 

 

 

 

 

0d

Odor countermeasure when

 

Do not set

 

 

 

indoor cooling thermostat is OFF

 

 

 

 

 

 

 

 

 

 

 

 

0E

Cool only

 

0

= Heat pump

1 = Cool only

 

 

 

 

 

 

 

0F

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

10

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

11

Multi-floor installation

 

Do not set

 

 

 

 

 

 

 

 

12

External Electronic Expansion Valve Kit

 

0 = No

1 = Yes

 

 

 

 

 

 

 

13

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

4E

Test mode 1

 

Do not set

 

 

4F

Test mode 2

 

Do not set

 

 

50

Demand 1

 

40%, 45% ... 100% ... 160%

 

 

 

 

 

 

51

Demand 2

 

40%, 45% ... 100% ... 160%

 

 

 

 

 

 

52

Current control level

 

40%, 45% ... 100% ... 160%, –1 (normal: at shipment from factory)

 

53

Control system schedule

 

Do not set

 

 

54

Control system schedule

 

Do not set

 

 

55

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

56

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

57

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

58

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

59

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

5A

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

5B

Control system schedule

 

Do not set

 

 

 

 

 

 

 

 

 

* Figures in parentheses indicate the data at the time of shipment from the factory.

SM831148

V-8

Page 168
Image 168