6. Test run
Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...)
Outdoor unit control PCB
System address rotary switch (Set to “0” at time of shipment)
System address rotary switch
System address
10s 20s DIP switch
ON ON
3 – 5HP
System address rotary switch
System address 10s digit and 20s digit
DIP switch
Automatic address button (black)
Terminal plug (black)
6
| 1 2 | OFF |
|
|
| |
|
|
| Fig. |
|
| |
| System address No. | System address 10s digit | System address 1s place | |||
| (2P DIP switch) |
| (Rotary switch) | |||
|
|
|
| |||
0 | Automatic address | ON |
| ON | ||
Both OFF |
| “0” setting | ||||
(Setting at shipment = “0”) |
| |||||
1 | 2 | OFF | ||||
|
|
| ||||
|
|
| ON |
| ON | |
1 | (If outdoor unit is No. 1) | Both OFF |
| “1” setting | ||
|
|
| 1 | 2 | OFF | |
|
|
| ON |
| ON | |
2 | (If outdoor unit is No. 2) | Both OFF |
| “2” setting | ||
|
|
| 1 | 2 | OFF | |
|
|
| ON |
| ON | |
11 | (If outdoor unit is No. 11) | 10s digit ON |
| “1” setting | ||
|
|
| 1 | 2 | OFF | |
|
|
| ON |
| ON | |
21 | (If outdoor unit is No. 21) | 20s digit ON |
| “1” setting | ||
|
|
| 1 | 2 | OFF | |
|
|
| ON |
| ON | |
30 | (If outdoor unit is No. 30) | 10s digit and 20s digit ON |
| “0” setting | ||
|
|
|
|
| ||
|
|
| 1 | 2 | OFF |
Automatic address setting using the remote controller
When the outdoor unit shown in “Basic wiring diagram 2” is used for group control of multiple outdoor units , use the remote controller to perform automatic address setting. (During automatic address setting, “SETTING” blinks on the remote controller display.)
Press the remote controller timer time button and
button simultaneously. (Hold for 4 seconds or longer.) Then press the
button. (Item code “AA” appears: All systems automatic address setting.)
(Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30. When automatic address setting is completed, the units return to normal stopped status.)
To select each refrigerant system individually and perform automatic address setting, press the remote controller timer time button and
button simultaneously. (Hold for 4 seconds or longer.) Then press either the tempera- ture setting
or
button. (Item code “A1” appears: Individual system automatic address setting)
Use either the or
button to select the outdoor unit to perform automatic address setting. (For example, when selected R.C.1 “R.C.1” is displayed.) Then press the
button. (Automatic address setting is performed for refrigerant circuit 1.) When automatic address setting for circuit 1 is completed, the system returns to normal stopped status. When automatic address setting for circuit 1 is completed, the system returns to normal stopped status. In the same way, press the remote controller timer time
button and
button simultaneously to per- form automatic address setting for a different R.C. (refrigerant circuit) if necessary. Then in the same way as
above (use the button to display “R.C.2,” for example), select the next circuit and perform automatic ad- dress setting.