1-1 Unit Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-Way Air Discharge Semi-Concealed Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

XH2672R

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

CH2672R

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

230 - 208 V / 1 Phase / 60 Hz

 

 

PERFORMANCE

 

Cooling

 

 

 

 

 

 

Heating

 

 

Capacity * [minimum~muximum]

 

BTU / h

24,800 [9,500~24,800]

 

 

29,800 [8,000~29,800]

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18,300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

8.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

 

 

 

 

 

710 / 530 / 450

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

14.1

 

 

 

 

 

 

 

 

10.5

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

208

 

 

230

 

 

208

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

 

 

VAC 187 - 253

 

 

Max. Running amperes*

 

 

A

15.6

 

 

 

 

 

 

17.3

 

 

14.8

 

 

16.4

 

 

Power input

 

 

W

2,920

 

 

 

 

 

 

2,920

 

 

2,790

 

 

2,790

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

2,200

 

2,200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

 

 

 

 

15 / 30

 

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

3 and Automatic control / Variable

 

 

Optional Wired Remote Controller

 

RCS-SH80UG / RCS-TM80BG

 

 

Optional Wireless Remote Controller

 

RCS-SH80UA.WL / RCS-BH80UA. WL

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

Rotary(SANYO)

 

 

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

 

 

 

 

38 / 35 / 31

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

49

 

 

 

 

 

 

 

Refrigerant control

 

 

 

Electronic Expansion Valve (MOV)

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

 

 

 

 

165 (50)

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

 

 

 

 

 

10~100 (3~30)

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

 

 

 

 

3 / 8 (6.35)

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

 

 

 

 

5 / 8 (15.88)

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

4.19 (1.9) - R410A

 

 

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

Outdoor unit

 

 

Unit dimensions

Height

 

in. (mm)

13-5/16 (338)

 

 

 

 

 

 

30- 23/32 (780)

 

 

 

 

Width

 

in. (mm)

33-55/64 (860)

 

 

 

 

 

 

37 (940)

 

 

 

 

Depth

 

in. (mm)

33-55/64 (860)

 

 

 

 

 

 

13- 3/8 (340)

 

 

Package dimensions

 

 

 

Body

 

Panel

Outdoor unit

 

 

 

 

Height

 

in. (mm)

11-9/64 (283)

 

4-3/32 (104)

34- 31/32 (888)

 

 

 

 

Width

 

in. (mm)

32-7/8 (835)

 

37-61/64 (964)

39- 31/32 (1,015)

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

39-21/64 (999)

16- 3/32 (409)

 

 

Net weight

 

 

lbs. (kg)

49 (22)

 

 

 

 

 

11 (5)

 

128 (58)

 

 

Shipping weight

 

 

lbs. (kg)

57 (26)

 

 

 

 

 

18 (8)

 

148 (67)

 

 

Shipping volume

 

cu.ft. (m 3 )

7.1 (0.200)

 

 

3.6 (0.100)

 

13.0 (0.369)

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB

Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

SM831148

1

I-9

Page 13
Image 13
Sanyo XH2672R / C2672R, XH4272R / C4272R, UH2672R, XH3672R, UH3672R Unit Specifications Way Air Discharge Semi-Concealed Type