5. Outdoor unit maintenance remote control

5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures

<Operating procedure>

(1)Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode.

During temperature monitoring, “Service Monitor” is lit.

(The display and operations are the same as when monitor mode is started from the unit remote controller.)

(2) Press

 

the button and select the indoor unit to monitor.

(4)

 

 

(3)Use the temperature setting and buttons to select the item code of the temperature to monitor.

The selected indoor unit No. and the temperature data are displayed.

(4)To end monitoring, press the button. The display returns to the normal display.

 

(3)

(1)

(2)

* The display does not blink.

 

Item code

Meaning of Code

 

 

 

Indoor unit data

02

Indoor unit intake temp.

 

 

 

 

03

Indoor unit heat exchanger temp. (E1)

 

 

 

 

04

Indoor unit heat exchanger temp. (E2)

 

 

 

 

05

 

 

 

 

06

Indoor unit discharge temp.

 

 

 

 

07

 

 

 

 

08

 

 

 

 

09

 

 

 

 

Outdoor unit data

0A

Discharge temp. (TD)

 

 

 

 

0b

 

 

 

 

0C

 

 

 

 

0d

Intake temp. (TS)

 

 

 

 

0E

Outdoor unit heat exchanger temp. (C1)

 

 

 

 

0F

Outdoor unit heat exchanger temp. (C2)

 

 

 

 

10

 

 

 

 

11

Outdoor air temp. (TO)

 

 

 

 

12

 

 

 

 

13

 

 

 

 

14

Current value

 

 

 

 

15

Outdoor MV value

 

 

 

 

19

Frequency

 

 

 

* Depending on the model, some items may not be displayed.