1-1 Unit Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-Way Air Discharge Semi-Concealed Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL No.

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

XH4272R

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

CH4272R

 

 

 

 

 

 

 

POWER SOURCE

 

 

 

 

230 - 208 V / 1 Phase / 60 Hz

 

 

PERFORMANCE

 

 

Cooling

 

 

 

 

 

 

 

 

 

Heating

 

 

Capacity * [minimum~muximum]

 

BTU / h

39,500 [9,500~39,500]

 

 

48,000 [8,000~48,000]

 

 

 

 

(17˚F)**

 

BTU / h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31,800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Moisture removal (High)

 

 

Pints / h

 

12.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation (H / M / L) 230 V

 

CFM

 

 

 

 

 

 

 

 

 

1050 / 840 / 720

 

 

 

 

 

 

 

External Static Pressure

 

 

in. WG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.E.E.R. / H.S.P.F. (Region 4)

 

BTU / Wh

 

14.6

 

 

 

 

 

 

 

 

 

 

10.4

 

 

ELECTRICAL RATINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage rating

 

 

V

230

 

 

 

 

 

 

 

 

208

 

 

230

 

 

 

208

 

 

Available voltage range

 

 

V

VAC 187 - 253

 

 

 

 

VAC 187 - 253

 

 

Max. Running amperes*

 

 

A

23.0

 

 

 

 

 

 

 

 

25.4

 

 

22.4

 

 

 

24.8

 

 

Power input

 

 

W

4,520

 

 

 

4,520

 

 

4,360

 

 

4,360

 

 

 

 

(17˚F)**

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

3,540

 

 

3,540

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back-up Heater

 

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum overcurrent protection (Indoor/Outdoor)

 

A

 

 

 

 

 

 

 

 

 

15 / 40

 

 

 

 

 

 

 

 

FEATURES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls

 

 

 

 

 

 

 

 

 

 

 

 

 

Microprocessor

 

 

 

 

 

 

Low ambient control

 

 

 

 

 

 

 

 

 

 

 

 

 

Built-in 0˚F

 

 

 

 

 

 

Fan speeds Indoor / Outdoor

 

 

3 and Automatic control / Variable

 

 

Optional Wired Remote Controller

 

 

RCS-SH80UG / RCS-TM80BG

 

 

Optional Wireless Remote Controller

 

RCS-SH80UA. WL / RCS-BH80UA. WL

 

 

Air deflection (Horizontal / Vertical )

 

 

 

 

 

 

 

 

 

 

 

/ Automatic (Vertical )

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter

 

 

 

 

 

 

Washable, long life (2,500 hr)

 

 

Drain pump (Drain connection)

 

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Rotary(SANYO)

 

 

 

 

 

 

Operation sound

Indoor - Hi/Me/Lo

 

dB - A

 

 

 

 

 

 

 

 

 

45 / 38 / 34

 

 

 

 

 

 

 

 

 

Outdoor - Hi

 

dB - A

 

 

 

 

 

 

 

 

 

 

 

 

53

 

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Electronic Expansion Valve (MOV)

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit of tubing length

 

 

ft. (m)

 

 

 

 

 

 

 

 

 

165 (50)

 

 

 

 

 

 

 

 

Limit of tubing length at shipment

 

ft. (m)

 

 

 

 

 

 

 

 

 

10~100 (3~30)

 

 

 

 

 

 

 

Limit of elevation difference

 

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

 

 

between the two units

 

 

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

 

 

Refrigerant tube

Narrow tube

 

in. (mm)

 

 

 

 

 

 

 

 

 

3 / 8 (6.35)

 

 

 

 

 

 

 

outer diameter

Wide tube

 

in. (mm)

 

 

 

 

 

 

 

 

 

5 / 8 (15.88)

 

 

 

 

 

 

 

Refrigerant amount at shipment

 

lbs. (kg)

 

 

 

 

 

 

 

 

 

7.94 (3.6) - R410A

 

 

 

 

 

 

DIMENSIONS & WEIGHT

 

 

 

Indoor unit (Include panel)

 

Outdoor unit

 

 

Unit dimensions

Height

 

in. (mm)

 

14-31/64 (368)

 

 

 

 

 

 

 

48-7/16 (1,230 )

 

 

 

 

Width

 

in. (mm)

 

45-9/32 (1,150)

 

 

 

 

 

 

37 (940)

 

 

 

 

Depth

 

in. (mm)

 

33-55/64 (860)

 

 

 

 

 

 

 

13- 3/8 (340)

 

 

Package dimensions

 

 

 

Body

 

Panel

 

Outdoor unit

 

 

 

 

Height

 

in. (mm)

12-13/32 (315)

 

 

4-3/32 (104)

 

52-3/8 (1,330 )

 

 

 

 

Width

 

in. (mm)

44-19/64 (1,125)

 

49-31/64 (1,257)

39- 31/32 (1,015)

 

 

 

 

Depth

 

in. (mm)

33-9/32 (845)

 

 

39-21/64 (999)

 

16- 3/32 (409)

 

 

Net weight

 

 

lbs. (kg)

60 (27)

 

 

 

 

 

 

16 (7)

 

 

220 (100)

 

 

Shipping weight

 

 

lbs. (kg)

71 (32)

 

 

 

 

 

 

22 (10)

 

 

240 (109 )

 

 

Shipping volume

 

cu.ft. (m 3 )

10.6 (0.299)

 

 

4.6 (0.131)

 

 

19.5 (0.552 )

 

 

 

 

 

 

 

DATA SUBJECT

TO CHANGE

WITHOUT NOTICE.

 

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB

Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

SM831148

1

I-11

Page 15
Image 15