4. Service procedures

4-1. Meaning of Alarm Messages

(1) Contents of remote controller switch alarm display

ON: Blinking: OFF:

4

Wired

Wireless

remote

remote controller

control

receiver display

display

 

 

Possible cause of malfunction

 

Operation

Timer

Standby

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Serial commu-

Remote controller is

 

Error in receiving serial communication signal

E01

 

 

 

 

 

nication errors

detecting error signal from

 

(Signal from main indoor unit in case of group control)

 

 

 

 

 

 

 

 

 

Mis-setting

indoor unit

 

Outdoor system address, indoor system address, or indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

individual/main/sub setting is not set

 

 

 

 

 

 

 

 

 

 

 

 

(Automatic address setting is not completed)

 

 

 

 

 

 

 

 

 

 

 

 

Auto address is not completed

 

 

 

 

 

 

 

 

 

 

 

 

Error in transmitting serial communication signal

E02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit is detecting error signal from remote controller (and system controller)

E03

 

 

 

 

 

 

Improper setting of indoor

 

Indoor unit address setting is duplicated

E08

 

 

 

 

 

 

 

 

 

 

 

 

 

unit or remote controller

 

Remote controller setting is duplicated

E09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit is detecting error

 

Error in transmitting serial communications signal

E10

 

 

 

 

 

 

signaled from signal option

 

Error in receiving serial communications signal

E11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address setting

 

Starting auto address setting is prohibited

 

 

 

 

 

 

 

 

 

 

failed

 

This alarm message shows that the auto address connector

E12

 

 

 

 

 

 

 

 

CN100 is shorted while other RC line is executing auto address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit capacity too low

E15

 

 

 

 

 

 

 

 

Indoor unit capacity too high

E16

 

 

 

 

 

 

Setting error

 

No indoor units connected

E20

 

 

 

 

 

 

 

Main unit duplication in simultaneous-operation multi control

E14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(detected by outdoor unit)

 

 

 

 

 

 

 

 

 

 

Indoor unit is detecting error

 

Error in receiving serial communications signal

E04

 

 

 

 

 

 

signaled from outdoor unit

 

Error in transmitting serial communications signal

E05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit is detecting

 

Error in receiving serial communications signal (including unit

E06

 

 

 

 

 

 

error signaled from indoor

 

quantity verification failure)

 

 

 

 

 

 

 

 

 

 

unit

 

Error in transmitting serial communications signal

E07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

An indoor unit detected

 

Error in transmitting serial communications signal

E17

 

 

 

 

 

 

trouble in the signal from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

another indoor unit

 

Error in receiving serial communications signal

E18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communications trouble

 

Communications failure with MDC

E31

 

 

 

 

 

 

 

 

 

 

 

 

between units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mis-setting

Setting error

 

Indoor unit group settings error

L01

 

 

 

 

 

 

 

 

Indoor/outdoor unit type mismatch

 

 

 

 

 

 

 

 

 

L02

 

 

 

 

 

 

 

 

 

 

 

 

 

Simultaneously

 

 

 

 

 

 

Main unit duplication in group control (detected by indoor unit)

L03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit address duplication (system address)

 

 

 

 

 

 

 

 

 

L04

 

 

 

 

 

 

 

 

 

 

 

 

 

Simultaneously

 

 

 

 

 

 

Group wiring connected for independent indoor unit

L07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Address not set or group not set

 

 

 

 

 

 

 

 

 

L08

 

 

 

 

 

 

 

 

 

 

 

 

 

Simultaneously

 

 

 

 

 

 

Indoor unit capacity not set

L09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit capacity not set or setting error

L10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Miswiring in group control wiring

 

 

 

 

 

 

 

 

 

 

 

L11

Simultaneously

 

 

 

 

 

 

Indoor unit type setting error (capacity)

L13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continued

SM831148

IV-2

Page 148
Image 148
Sanyo TH4272R / C4272R Service procedures Meaning of Alarm Messages, Contents of remote controller switch alarm display