4. Service procedures

4-3. Details of Alarm Messages

(1) [Alarm “P29”]

Input power detection circuit trouble

(MDC trouble)

Compressor does not run.

 

 

Breakdown

 

Motor current detection circuit trouble

4

Is power OK?

No

Correct power line.

 

Yes

 

 

Is

 

 

current

No

Check and correct

detection

circuit wiring

 

wiring.

OK?

 

 

Are

 

 

wiring and

No

Check and correct

connector

 

wiring.

connections

 

 

 

OK?

 

 

Yes

 

 

Is No compressor

OK?

Ground Yes

fault?

Yes

Coil

resistor Yes short circuit?

Coil open

Yes

 

circuit?

 

No

 

Is there

abnormal refrigerant No Replace

accumulation?compressor.

Yes

 

 

Is

 

Are

operation of

 

No

C1 and TS No

electronic

 

sensors

control valve

 

 

OK?

OK?

 

 

 

Yes

 

Replace electronic

 

 

 

 

control valve.

Is there overload?

No

Remove

 

the cause.

 

 

Yes

 

 

Replace outdoor

 

 

unit control PCB.

 

 

IV-8

Replace compressor.

Replace C1 and

TS sensors.

SM831148

Page 154
Image 154
Sanyo TH2672R, XH4272R / C4272R, UH2672R, XH2672R Service procedures Details of Alarm Messages, Alarm P29, MDC trouble