(3)During initial communication (startup of the system)

Lighting error code 6F(H)

- When the master station indicates error code 6F(H) and the COMM lamp is OFF.

The cause may be a parameter setting error of the master station. Check the master station parameters below.

Parameter address(8)

Setting item

Reference page of the

setting contents

004000 to 004001

Relay link top address

 

of master station

 

 

 

 

 

 

004002

Amount of connectable

 

stations

 

 

 

 

 

 

004400 to 004403

Register link top address

 

of master station

11-5 to 9

 

 

005000 to 050001

Relay link transmit

 

bytes of master station

 

 

 

 

 

 

005200 to 005201

Register link transmit

 

bytes of master station

 

 

 

 

007764 to 007767

Flag top address

 

 

 

 

-When the master station indicates error code 6F(H) and the COMM lamp lights.

The cause may be a setting error of any of the slave stations which are set in the parameter. Check the following master station parameters.

Parameter address(8)

Setting item

Reference page of the

setting contents

004004 to 004377

Relay link top address of

 

each slave station.

 

 

Number of offset bytes.

 

 

 

 

004404 to 004777

Register link top address

11-5 to 9

of each slave station.

 

Number of offset bytes.

 

 

 

 

005002 to 005177

Relay link transmit bytes

 

of each slave station

 

 

 

 

 

 

005202 to 005377

Register link transmit

 

bytes of each slave station

 

 

 

 

 

 

When slave station is JW-21MN, see "Chapter 11: Setting of Switches and Parameter" for setting range.

-When the master station is normal and the error code 6F(H) of a slave station lights.

The cause may be a faulty setting of the slave station parameter. Check the following slave station parameters.

 

 

 

16

Parameter address(8)

Setting item

Reference page of the

 

 

 

 

007764 to 007767

Flag top address

11- 22

 

 

 

 

 

 

 

When slave station is JW-21MN, see "Chapter 11: Setting of Switches and Parameter" for setting range.

16-5