(3)During initial communication (startup of the system)
Lighting error code 6F(H)
- When the master station indicates error code 6F(H) and the COMM lamp is OFF.
The cause may be a parameter setting error of the master station. Check the master station parameters below.
Parameter address(8) | Setting item | Reference page of the | |
setting contents | |||
004000 to 004001 | Relay link top address |
| |
of master station |
| ||
|
| ||
|
|
| |
004002 | Amount of connectable |
| |
stations |
| ||
|
| ||
|
|
| |
004400 to 004403 | Register link top address |
| |
of master station | |||
|
| ||
005000 to 050001 | Relay link transmit | ||
| |||
bytes of master station |
| ||
|
| ||
|
|
| |
005200 to 005201 | Register link transmit |
| |
bytes of master station |
| ||
|
|
| |
007764 to 007767 | Flag top address |
| |
|
|
|
-When the master station indicates error code 6F(H) and the COMM lamp lights.
The cause may be a setting error of any of the slave stations which are set in the parameter. Check the following master station parameters.
Parameter address(8) | Setting item | Reference page of the |
setting contents | ||
004004 to 004377 | Relay link top address of |
|
each slave station. |
| |
| Number of offset bytes. |
|
|
|
|
004404 to 004777 | Register link top address | |
of each slave station. | ||
| Number of offset bytes. |
|
|
|
|
005002 to 005177 | Relay link transmit bytes |
|
of each slave station |
| |
|
| |
|
|
|
005202 to 005377 | Register link transmit |
|
bytes of each slave station |
| |
|
| |
|
|
|
When slave station is
-When the master station is normal and the error code 6F(H) of a slave station lights.
The cause may be a faulty setting of the slave station parameter. Check the following slave station parameters.
|
|
| 16 | ||
Parameter address(8) | Setting item | Reference page of the | |||
| |||||
|
|
| |||
007764 to 007767 | Flag top address | 11- 22 |
|
| |
|
|
|
|
|
When slave station is