From the previous page

 

 

 

 

 

 

 

 

Set top address of the relay link area on the master station

[OCT (octal), word]

 

 

 

 

 

 

 

Set file address(8) to parameter address 004000 to 004001(8).

004000(8)

 

 

 

0 0

0 2 1 0 (8)

 

- In case of setting 0210 (file address 000210(8))

004001(8)

 

 

 

 

(Example for page 11-10)

 

 

 

Screen display of JW-14PG

 

(Word display)

 

03774

0

000000

 

 

03776

0

000000

Display the contents of address

 

After converting to octal,

 

I PARAM.

 

 

004000(8)

 

write the data 000210.

 

 

 

>04000

0

000210

 

 

 

Data link function setting

[HEX (hexadecimal), byte]

004002(8)

 

0 1 (H)

 

 

 

 

 

Screen display of JW-14PG

 

Set "01(H) (=001(8))" in parameter address 004002(8) and change to

 

"relay/register link" function.

 

04000

 

HEX

880

 

 

 

 

 

04001

 

HEX

00F

 

 

 

 

 

I PARAM.

 

 

 

 

 

 

 

>04002

 

HEX

01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set number of connecting stations

[DCM (decimal), byte]

004003(8)

 

0 0 3 (D)

Set the number of connecting stations (02 to 64(D)) including the master station in the parameter address 004003(8) by octal.

-In case of setting in 3 sets (003(D)) (Example for page 11-10)

Screen display of JW-14PG

04001

DCM

000

 

 

04002

DCM

001

 

 

I PARAM.

 

 

 

 

 

 

 

11

>04003

DCM

003

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set top address of relay link area on slave station (01 to 77) (at standard function)/number of

offset bytes (at save memory function)

Set in parameter addresses 004004 to 004377(8). These top addresses should not overlap the register link area, flag area, or any area used by other option module.

Slave

 

004004(8)

Lower

 

 

 

 

 

 

 

 

 

 

 

004005(8)

Upper

 

 

 

station

 

 

 

004006(8)

00(H)

 

 

 

01

 

 

 

 

 

004007(8)

·

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slave

 

004374(8)

Lower

 

 

 

 

 

004375(8)

Upper

 

 

station

 

 

004376(8)

00(H)

 

 

77(8)

 

 

 

 

004377(8)

·

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In case of standard function, set top address by file address(8). In case of save memory function, set number of offset bytes.

00(H): The top address is the same address of the master station regardless of the value set at of 004004 to 004005(8).

80(H): The top address is different from the address of the master station (Offset is valid).

For the save memory function, set in 80(H).

00(H)

80(H)

-In case of setting 0200 (file address 000200(8)) in parameter addresses 004004 to 004007(8) (slave station 01) and set 4 (number of off set bytes) in 004010(8) to 004013(8) (slave station 02). (Example for page 11-10.)

To the next page

11-15