11

11-4 Setting slave station parameters (common for all slave stations)

When the JW-21MN is used as a slave station, set the following items for parameters.

[1] Setting contents

 

 

 

 

Setting item

 

 

Initial

Contents

Corresponding

 

 

 

 

 

Address(8)

signs on pages

 

 

 

 

 

value (H)

 

 

 

 

 

11-7 to 11-9

 

 

 

 

Number of receiving bytes of

 

 

Set the number of bytes by decimals. (0 to 256)

 

 

 

 

 

 

①

relay link in save memory

 

007720

00

- If 0 is set, the number of bytes will be the same

h1 to hn

 

 

 

function

 

007721

as the number of the sending bytes which is set

 

 

 

 

 

V2

 

in the master station

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1

 

 

 

 

 

 

 

 

 

 

 

 

Number of receiving bytes of

 

 

Set the number of bytes by decimals. (0 to 2048)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

②

register link in save memory

007722

00

- If 0 is set, the number of bytes will be the same

i1 to in

 

 

 

function

 

007723

as the number of the sending bytes which is set

 

 

 

 

 

V2

 

 

in the master station

 

 

 

 

*2

③

Whether the station number

 

00

Store the number of own statin in the data memory

 

 

 

information should be output

007763

when setting on 01(H). (storage area of 1 byte follows

 

 

 

 

 

 

 

 

 

 

or not

V2

 

 

flag area of 24 bytes, valid when 007767(8) is 80(H))

 

 

 

 

 

 

 

 

 

007764

E0

Lower of file address

 

Initial value: 01E0(H)

 

 

 

 

 

 

 

Top address of flag area

 

007765

01

 

 

↓

 

 

 

 

 

 

④

 

Upper of file address

 

000740(8) (コ0740)

e1 to en

 

 

 

(communication and PC

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

operation condition monitor

007766

File number

 

 

 

 

 

 

 

 

flag)

 

007767

80

Flag output (Yes: 80(H) No: 00(H))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00(H): Stop operation

 

 

 

 

 

 

 

 

- Start/stop operation of the

 

 

01(H): Start operation

 

 

 

 

 

 

 

⑤

JW-21MN

 

007777

01

80(H): Writing to the EEPROM, stop operation

 

 

 

 

 

 

- Writing to EEPROM of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JW-21MN

 

 

 

81(H): Writing to the EEPROM, start operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08(H): Parameter initializing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1: Set only when the memory capacity save function is used.

*2: "Whether the station number information should be output or not" is a unique function of the JW-21MN.

-Parameter addresses other than above mentioned are reserved areas and prohibited to be changed.

-When any slave stations are except JW-21MN, see the instruction manual of each device.

11-22

Page 75
Image 75
Sharp JW-21MN manual 11-22, Setting item, Contents