From the previous page

Set top address of flag area

File address: OCT (octal), word

File number/flag: HEX (hexadecimal), byte

Set the top address of the flag area (24 bytes) in order to monitor the communication condition and PC operation condition on the parameter address 007764 to 007767(8).

Flag area uses 24 bytes regardless number of connecting stations.

007764(8)

Lower

 

 

 

007765(8)

Upper

 

 

 

007766(8)

 

 

 

 

 

File number

 

 

 

007767(8)

 

 

 

 

00(H): Do not output flag

 

 

 

 

 

 

 

 

 

 

 

 

 

80(H): Output flag

 

 

 

 

 

 

 

 

-In case of setting 0740 (file address 000740(8)), "output flag" in parameter address 007764 to 007767(8). (Slave station 01 of page 11-10)

(Word display)

Write "000740(8)" in parameter addresses 007764 to 007765(8).

Write 000(8) (=00(H)) in parameter address 007766(8).

Write 80(H) in parameter address 007767(8).

Covert to

 

 

 

 

 

 

 

hexadecimal

 

 

 

 

 

 

 

figures

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

Screen display of JW-14PG

007764(8)

 

 

 

 

 

 

000740(8)

 

 

 

07765

HEX

01

 

 

 

 

 

007765(8)

 

 

 

07766

HEX

00

 

 

 

 

 

 

 

 

 

 

 

I PARAM.

 

 

 

007766(8)

00(H)

 

 

>07767

HEX

80

 

007767(8)

 

 

 

80(H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To next page