8-2 Memory addresses for computer links

-Data memory byte addresses in the computer link must be entered the same way a data link address is entered.

-The relay numbers and TMR/CNT numbers are the same for the ME-NET. However the TMR/CNT contact points correspond to the even addresses from 16000 to 17777(8).

-Program addresses correspond to addresses of file (SEG)8.

For details about the detailed addresses to use on the host computer, see the instruction manual for the host computer.

(1) Memory address map (against JW20/JW20H)

 

 

 

JW20/20H

ME-NET address(8)

Capacity

Remarks

 

 

 

address(8)

 

 

 

 

 

 

I/O relay

 

00000 to 03777

SEG0 00000.0 to 00377.7

2048 points

 

 

 

 

 

 

 

Auxiliary relay/JW20H

04000 to 06777

SEG0 00400.0 to 00677.7

1536 points

 

 

 

 

 

 

Bit

Latched relay

07000 to 07777

SEG0 00700.0 to 00777.7

512 points

 

 

 

 

 

 

address

General-purpose relay

10000 to 15777

SEG0 01000.0 to 01577.7

3072 points

 

 

 

 

 

 

 

 

TMR/CNT contact point

T-C000 to T-C777

Even addresses of SEG0

512 points

 

01600.0 to 01777.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O relay

 

0000 to 0377

SEG0 00000 to 00377

256 bytes

 

 

 

 

 

 

 

 

Auxiliary relay

0400 to 0677

SEG0 00400 to 00677

192 bytes

 

 

 

 

 

 

 

 

Latched relay

0700 to 0777

SEG0 00700 to 00777

64 bytes

 

 

 

 

 

 

 

 

General-purpose relay

1000 to 1577

SEG0 01000 to 01577

384 bytes

 

 

 

 

 

 

 

TMR/CNT current value

b0000 to b1777

SEG0 02000 to 03777

1024 bytes

 

 

 

 

 

 

 

 

 

09000 to 09777

SEG0 04000 to 04777

512 bytes

 

 

 

 

 

 

 

 

 

19000 to 19777

SEG0 05000 to 05777

512 bytes

 

 

 

 

 

 

 

 

 

29000 to 29777

SEG0 06000 to 06777

512 bytes

Byte

 

 

 

 

 

 

 

 

39000 to 39777

SEG0 07000 to 07777

512 bytes

address

 

 

 

 

 

 

 

 

 

 

 

49000 to 49777

SEG0 10000 to 10777

512 bytes

 

Register

 

 

 

 

 

 

59000 to 59777

SEG0 11000 to 11777

512 bytes

 

 

 

 

 

 

 

 

 

69000 to 69777

SEG0 12000 to 12777

512 bytes

 

 

 

 

 

 

 

 

 

79000 to 79777

SEG0 13000 to 13777

512 bytes

 

 

 

 

 

 

 

 

 

89000 to 89777

SEG0 14000 to 14777

512 bytes

 

 

 

 

 

 

 

 

 

99000 to 99777

SEG0 15000 to 15777

512 bytes

 

 

 

 

 

 

 

 

 

E0000 to E1777

SEG0 16000 to 17777

1024 bytes

 

 

 

 

 

 

 

 

TMR/CNT number

 

000 to 777

0000 to 0777

512 pieces

-----

 

 

 

 

 

 

Program

JW-21CU/22CU

000000 to 006777

SEG8 000000 to 006777

3584 step

-----

 

 

 

 

 

 

address

JW-22CU

000000 to 016777

SEG8 000000 to 016777

7680 step

-----

 

 

 

 

 

 

 

 

-Relay addresses 07300 to 07377(8) and 15760 to 15767(8) in the JW20/JW20H are special address ranges for relays.

-Available addresses vary with PC model on which the JW-21MN is installed and its capacity. For details, see an instruction manual for each PC.

8

8-3

Page 31
Image 31
Sharp JW-21MN manual Memory addresses for computer links, JW20/20H ME-NET address Capacity