11-2 Switch setting of master station and slave station
Prior to using the
[1] Mode switch (MODE)
Set whether the
Station | Data link | Setting value of | |
the mode switch | |||
|
| ||
Master station | Standard function | 2 | |
|
|
| |
Slave station | Standard function | 2 | |
|
| ||
Save memory function | 3 | ||
| |||
|
|
|
- Do not set the mode switch to "0," "1," or "4" to "F. - The computer link function is effective for both "2"
and "3" settings.
3456 | |
2 | 7 |
01 | 8 |
F | |
E | 9 |
A | |
DCB |
| 2 | 3 | 4 | 5 |
|
|
|
|
|
|
| 7 |
| ||
1 |
|
|
| 6 | MODE | ||
|
|
|
|
| 8 | ||
F |
|
|
| ||||
0 |
|
|
|
|
| ||
| E |
|
| A | 9 |
| |
|
| DC |
|
|
|
| |
|
|
| B |
|
|
|
(Factory setting: 2)
(Rear side)
[2] Module No. switch (UNIT NO.)
Select error history storage registration area and data link (save memory function) area for a slave station by setting the mode switches.
| (1) Setting the mode switch to "2" |
| |||
|
|
|
|
| |
|
| Setting value of the | Error history storage register | ||
11 | |||||
| module No. switch | JW20/JW20H | JW30H | ||
|
| ||||
|
| 0 | E1400 to E1577 | E7400 to E7577 | |
|
| 1 | E1200 to E1377 | E7200 to E7377 | |
|
| 2 | E1000 to E1177 | E7000 to E7177 | |
|
| 3 | E0600 to E0777 | E6600 to E6777 | |
|
| 4 | E0400 to E0577 | E6400 to E6577 | |
|
| 5 | E0200 to E0377 | E6200 to E6377 | |
|
| 6 | E0000 to E0177 | E6000 to E6177 | |
|
| 7 to 9 | Prohibited setting |
(2) Setting the mode switch to "3"
UNIT | 6 | 7 | 8 |
| 9 | ||
|
| 0 | |
NO. | 5 |
| |
4 |
| 1 | |
| 3 | ||
| 2 | ||
|
|
(Factory setting: 0)
(Front side)
Setting value of the | Data link (Save memory function) | Error history storage register | ||
module No. switch | Relay link area | Register link area | JW20/JW20H | JW30H |
0 | コ1000 to コ1077 | 09000 to 09777 | E1400 to E1577 | E7400 to E7577 |
1 | コ1100 to コ1177 | 19000 to 19777 | E1200 to E1377 | E7200 to E7377 |
2 | コ1200 to コ1277 | 29000 to 29777 | E1000 to E1177 | E7000 to E7177 |
3 | コ1300 to コ1377 | 39000 to 39777 | E0600 to E0777 | E6600 to E6777 |
4 | コ1400 to コ1477 | 49000 to 49777 | E0400 to E0577 | E6400 to E6577 |
5 to 9 |
| Prohibited setting |
|
-The setting value of the module No. switch should not be the same as any other option module (including
-The top address of each relay link area and register link area corresponds to f1 to fn and g1 to gn on page