11-2 Switch setting of master station and slave station

Prior to using the JW-21MN, set the following switches.

[1] Mode switch (MODE)

Set whether the JW-21MN is used as a master station or a slave station as well as the data link type (standard function or save memory function).

Station

Data link

Setting value of

the mode switch

 

 

Master station

Standard function

2

 

 

 

Slave station

Standard function

2

 

 

Save memory function

3

 

 

 

 

- Do not set the mode switch to "0," "1," or "4" to "F. - The computer link function is effective for both "2"

and "3" settings.

3456

2

7

01

8

F

E

9

A

DCB

 

2

3

4

5

 

 

 

 

 

 

 

7

 

1

 

 

 

6

MODE

 

 

 

 

 

8

F

 

 

 

0

 

 

 

 

 

 

E

 

 

A

9

 

 

 

DC

 

 

 

 

 

 

 

B

 

 

 

(Factory setting: 2)

(Rear side)

[2] Module No. switch (UNIT NO.)

Select error history storage registration area and data link (save memory function) area for a slave station by setting the mode switches.

 

(1) Setting the mode switch to "2"

 

 

 

 

 

 

 

 

Setting value of the

Error history storage register

11

 

module No. switch

JW20/JW20H

JW30H

 

 

 

 

0

E1400 to E1577

E7400 to E7577

 

 

1

E1200 to E1377

E7200 to E7377

 

 

2

E1000 to E1177

E7000 to E7177

 

 

3

E0600 to E0777

E6600 to E6777

 

 

4

E0400 to E0577

E6400 to E6577

 

 

5

E0200 to E0377

E6200 to E6377

 

 

6

E0000 to E0177

E6000 to E6177

 

 

7 to 9

Prohibited setting

(2) Setting the mode switch to "3"

UNIT

6

7

8

 

9

 

 

0

NO.

5

 

4

 

1

 

3

 

2

 

 

(Factory setting: 0)

(Front side)

Setting value of the

Data link (Save memory function)

Error history storage register

module No. switch

Relay link area

Register link area

JW20/JW20H

JW30H

0

1000 to 1077

09000 to 09777

E1400 to E1577

E7400 to E7577

1

1100 to 1177

19000 to 19777

E1200 to E1377

E7200 to E7377

2

1200 to 1277

29000 to 29777

E1000 to E1177

E7000 to E7177

3

1300 to 1377

39000 to 39777

E0600 to E0777

E6600 to E6777

4

1400 to 1477

49000 to 49777

E0400 to E0577

E6400 to E6577

5 to 9

 

Prohibited setting

 

-The setting value of the module No. switch should not be the same as any other option module (including JW-21MN) mounted on the same basic rack panel.

-The top address of each relay link area and register link area corresponds to f1 to fn and g1 to gn on page 11-8 and 11-9.

11-2