- If the bus cable between the slave station 05(8) and 06(8) is disconnected in the following system.

03(8)

02(8)

01(8)

04(8)

Master

05(8)

06(8)

07(8)

station

 

 

 

 

B A

C

D

 

 

 

 

 

 

Disconnection

 

State of an individual communication flag

 

 

 

D7 6

5

4 3 2

1 D0

 

 

 

 

OFF

 

Unstable

OFF

 

 

 

 

Remove the connector on point A, and turn ON the termination resistance of the master station.

As the communication possible stations 03(8), 02(8), 01(8), and 04(8) are normal, the state of communication monitoring flag is as follows.

D7 6 5 4 3 2 1 D0

OFF ON

Connect the A connector, and

As the one side of the termination

then remove the connector on

resistance is lost, all of the

point B.

communication possible stations 05(8),

 

06(8), and 07(8) are abnormal, and the

 

 

station 05(8) is unstable.

 

D7 6 5 4 3 2 1 D0

16

Remove the connector on point C and make sure the B connector is not connected. Turn ON the termination resistance of the slave module 05(8).

Connect the C connector and make sure the B connector is not connected, and remove the connector at the next point to the point D.

Turn OFF the termination resistance of the slave station 05(8), and turn ON the termination resistance of the end station 06(8).

OFF Unstable OFF ON

As the communication possible station 05(8) is normal, abnormal points exists ahead of the point C.

D7 6 5

4 3 2

1 D0

OFF ON

OFF

ON

As the one side of the termination resistance is lost, the station 05(8) and 06(8) become communication possible stations, but the station 05(8) is unstable and the station 06(8) is turned to OFF, so the abnormal states occur between the point C and the point D.

D7 6 5 4 3 2 1 D0

OFF Unstable OFF ON

Cause

Countermeasure

Disconnection in the bus cable and the

Remove both the bus cable and

branch cable between the station 05(8) and

the branch cable connectors. After

06(8), or contact failure of the connectors

that, shorten one of these

 

connectors and check conductivity

 

using a tester.

 

 

Error on the slave station 06(8)

Exchange the slave module.

 

 

16-4

Page 99
Image 99