(2)Check cable/connector

As errors on the junction from the main cable to the drop cable or the contact failure on the connecting point of each station or errors of the master module are assumed, check with the following procedure.

YES

UNT. E lamp turns ON

 

Exchange master module

 

NO

Monitor individual communication flag See page 12-2in support tool.

Error only 1 station

NO

Check and exchange the bus YES cable and branch cable to the station with the error or the

station error module where the error occurred.

At plural station error

See next page

16

16-3