York R-410A ZH/ZJ/ZR Series manual ZH078 6.5 Ton Bottom Duct, ZH090 7.5 Ton Bottom Duct

Models: R-410A ZH/ZJ/ZR Series

1 206
Download 206 pages 7.86 Kb
Page 108
Image 108
ZH078 (6.5 Ton) Bottom Duct

528150-YTG-G-1210

ZH078 (6.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

0.6

 

0.8

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP RPM BHP

 

 

Field Supplied Drive

 

Standard 1.5 HP & Drive

 

 

Hi Static 2 HP & Drive

 

 

 

 

 

1800

775

0.31

850

0.53

924

0.72

998

0.89

1072

1.05

1147

1.20

1224

1.35

1303

1.51

1384

1.69

1469

1.89

2000

803

0.45

878

0.67

952

0.86

1026

1.03

1100

1.19

1175

1.34

1252

1.49

1331

1.65

1412

1.83

1497

2.03

2200

838

0.60

913

0.82

986

1.01

1060

1.19

1134

1.34

1210

1.49

1286

1.65

1365

1.81

1447

1.98

1532

2.18

2400

878

0.78

953

1.00

1027

1.19

1100

1.36

1174

1.52

1250

1.67

1327

1.82

1405

1.98

1487

2.16

-

-

2600

923

0.98

997

1.20

1071

1.39

1145

1.56

1219

1.72

1294

1.87

1371

2.02

1450

2.18

-

-

-

-

2800

971

1.20

1046

1.42

1119

1.61

1193

1.78

1267

1.94

1343

2.09

1419

2.24

-

-

-

-

-

-

3000

1023

1.44

1097

1.66

1171

1.85

1245

2.03

1319

2.18

-

-

-

-

-

-

-

-

-

-

3200

1077

1.71

1151

1.93

1225

2.12

1299

2.29

-

-

-

-

-

-

-

-

-

-

-

-

3400

1133

1.99

1208

2.21

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

2 HP & Field Supplied Drive

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZH090 (7.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

0.6

 

0.8

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

Field Supplied Drive

 

Standard 1.5 HP & Drive

 

 

Hi Static 3 HP & Drive

 

 

 

 

 

2000

803

0.45

878

0.67

952

0.86

1026

1.03

1100

1.19

1175

1.34

1252

1.49

1331

1.65

1412

1.83

1497

2.03

2200

838

0.60

913

0.82

986

1.01

1060

1.19

1134

1.34

1210

1.49

1286

1.65

1365

1.81

1447

1.98

1532

2.18

2400

878

0.78

953

1.00

1027

1.19

1100

1.36

1174

1.52

1250

1.67

1327

1.82

1405

1.98

1487

2.16

1572

2.36

2600

923

0.98

997

1.20

1071

1.39

1145

1.56

1219

1.72

1294

1.87

1371

2.02

1450

2.18

1532

2.36

1617

2.56

2800

971

1.20

1046

1.42

1119

1.61

1193

1.78

1267

1.94

1343

2.09

1419

2.24

1498

2.40

1580

2.58

1665

2.78

3000

1023

1.44

1097

1.66

1171

1.85

1245

2.03

1319

2.18

1394

2.33

1471

2.49

1550

2.65

1632

2.82

1717

3.02

3200

1077

1.71

1151

1.93

1225

2.12

1299

2.29

1373

2.45

1448

2.60

1525

2.75

1604

2.91

1686

3.09

1771

3.29

3400

1133

1.99

1208

2.21

1282

2.41

1356

2.58

1430

2.73

1505

2.88

1582

3.04

1661

3.20

1742

3.37

-

-

3600

1192

2.30

1267

2.52

1341

2.71

1414

2.88

1489

3.04

1564

3.19

1641

3.34

-

-

-

-

-

-

3800

1253

2.63

1327

2.85

1401

3.04

1475

3.21

1549

3.37

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZH102 (8.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

 

0.6

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

FS4

 

 

Standard 2 HP & Drive

 

 

 

 

 

Hi Static 3 HP & Drive

 

 

 

2600

674

0.71

731

0.88

786

1.05

838

1.24

887

1.42

933

1.59

974

1.74

1010

1.87

1040

1.97

1064

2.03

2800

689

0.86

746

1.02

801

1.20

854

1.38

903

1.56

948

1.73

989

1.88

1025

2.01

1056

2.11

1080

2.17

3000

707

1.01

764

1.17

819

1.35

872

1.53

921

1.71

966

1.88

1007

2.03

1043

2.16

1074

2.26

1098

2.32

3200

728

1.17

785

1.33

840

1.51

892

1.69

941

1.87

987

2.04

1028

2.20

1064

2.33

1094

2.42

1118

2.48

3400

751

1.34

808

1.51

863

1.68

915

1.87

964

2.05

1010

2.22

1051

2.37

1087

2.50

1117

2.60

1141

2.66

3600

776

1.53

833

1.70

888

1.87

941

2.06

990

2.24

1035

2.41

1076

2.56

1112

2.69

1142

2.79

1167

2.85

3800

804

1.74

861

1.90

916

2.08

969

2.26

1018

2.44

1063

2.61

1104

2.77

1140

2.90

1170

2.99

-

-

4000

835

1.97

892

2.13

947

2.31

999

2.49

1048

2.67

1094

2.84

1135

2.99

-

-

-

-

-

-

4200

867

2.21

924

2.37

979

2.55

1032

2.73

1081

2.91

1127

3.08

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

108

Johnson Controls Unitary Products

Page 108
Image 108
York R-410A ZH/ZJ/ZR Series manual ZH078 6.5 Ton Bottom Duct, ZH090 7.5 Ton Bottom Duct, ZH102 8.5 Ton Bottom Duct