York R-410A ZH/ZJ/ZR Series manual Indoor Blower Speed RPM

Models: R-410A ZH/ZJ/ZR Series

1 206
Download 206 pages 7.86 Kb
Page 126
Image 126
Manual background

528150-YTG-G-1210

UNIT DESCRIPTION / MODEL

 

ZH/ZJ/ZR061 / 5 Ton / Standard Static Belt Drive

 

TEST CONFIGURATION

 

Vertical (Bottom Return) Ducted Inlet

 

Indoor Blower Speed (RPM)

812 - 3 Turns Open Equivalent

915- 1 Turn Open Equivalent

External Static Pressure (IWG)

 

0.6

 

0.8

Airflow (CFM)

 

1575

 

1800

Blower Motor BHP

 

0.64

 

0.83

Octave Center Freq. Hz

ID Blower Only (dB)

Cooling Operation1 (dB)

ID Blower Only (dB)

Cooling Operation1 (dB)

63

75

78

80

80

125

66

80

69

81

250

59

66

62

65

500

60

60

63

63

1000

57

57

60

60

2000

52

53

55

55

4000

49

50

53

53

8000

44

45

47

47

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Indoor Sound Power Levels (Vertical Ducted Discharge, Standard Static Belt Drive)

UNIT DESCRIPTION / MODEL

 

ZH/ZJ/ZR037 / 3 Ton / Standard Static Belt Drive

 

TEST CONFIGURATION

 

Vertical (Bottom Supply) Ducted Discharge

 

Indoor Blower Speed (RPM)

609 - 3 Turns Open Equivalent

712 - 1 Turn Open Equivalent

External Static Pressure (IWG)

 

0.4

 

0.6

Airflow (CFM)

 

850

 

950

Blower Motor BHP

 

0.32

 

0.42

Octave Center Freq. Hz

ID Blower Only (dB)

Cooling Operation1 (dB)

ID Blower Only (dB)

Cooling Operation1 (dB)

63

76

77

81

81

125

68

68

72

72

250

55

65

57

57

500

56

57

57

57

1000

51

57

52

56

2000

49

49

50

50

4000

48

48

49

51

8000

46

46

47

48

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.