ZR078-150 Bottom Duct Application

528150-YTG-G-1210

ZR078-150 Bottom Duct Application

ZR078 (6.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

0.6

 

0.8

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

1.5 HP & Field Supplied Drive

 

Standard 1.5 HP & Drive

 

Hi Static 2 HP & Drive

 

 

 

 

 

 

1800

801

0.45

874

0.65

946

0.82

1018

0.97

1090

1.11

1163

1.25

1238

1.38

1315

1.52

1395

1.68

1477

1.86

2000

831

0.59

903

0.78

975

0.95

1047

1.10

1119

1.24

1193

1.38

1267

1.51

1344

1.66

1424

1.81

1507

1.99

2200

867

0.74

940

0.93

1012

1.10

1084

1.25

1156

1.39

1229

1.53

1304

1.66

1381

1.81

1461

1.96

1543

2.14

2400

910

0.91

983

1.10

1055

1.27

1126

1.43

1199

1.57

1272

1.70

1347

1.84

1424

1.98

1503

2.14

-

-

2600

957

1.10

1030

1.30

1102

1.47

1174

1.62

1246

1.76

1320

1.89

1394

2.03

1471

2.17

-

-

-

-

2800

1009

1.32

1082

1.51

1154

1.69

1225

1.84

1298

1.98

1371

2.11

1446

2.25

-

-

-

-

-

-

3000

1064

1.56

1137

1.75

1208

1.92

1280

2.08

1353

2.22

-

-

-

-

-

-

-

-

-

-

3200

1122

1.82

1194

2.02

1266

2.19

-

-

-

-

-

-

-

-

-

-

-

-

-

-

3400

1182

2.10

1254

2.30

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

2 HP & Field Supplied Drive

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZR090 (7.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

1.2

1.4

1.6

1.8

2.0

(CFM)

 

 

 

 

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1.5 HP & Field

 

 

Standard 1.5 HP & Drive

 

 

 

Hi Static 3 HP & Drive

 

 

 

 

 

 

Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

831

0.59

903

0.78

975

0.95

1047

1.10

1119

1.24

1193

1.38

1267

1.51

1344

1.66

1424

1.81

1507

1.99

2200

867

0.74

940

0.93

1012

1.10

1084

1.25

1156

1.39

1229

1.53

1304

1.66

1381

1.81

1461

1.96

1543

2.14

2400

910

0.91

983

1.10

1055

1.27

1126

1.43

1199

1.57

1272

1.70

1347

1.84

1424

1.98

1503

2.14

1586

2.31

2600

957

1.10

1030

1.30

1102

1.47

1174

1.62

1246

1.76

1320

1.89

1394

2.03

1471

2.17

1551

2.33

1634

2.51

2800

1009

1.32

1082

1.51

1154

1.69

1225

1.84

1298

1.98

1371

2.11

1446

2.25

1523

2.39

1602

2.55

1685

2.73

3000

1064

1.56

1137

1.75

1208

1.92

1280

2.08

1353

2.22

1426

2.35

1501

2.49

1578

2.63

1657

2.79

1740

2.96

3200

1122

1.82

1194

2.02

1266

2.19

1338

2.34

1410

2.48

1484

2.61

1559

2.75

1636

2.89

1715

3.05

1798

3.23

3400

1182

2.10

1254

2.30

1326

2.47

1398

2.62

1471

2.76

1544

2.90

1619

3.03

1696

3.17

1775

3.33

-

-

3600

1244

2.41

1317

2.60

1389

2.77

1461

2.93

1533

3.07

1606

3.20

1681

3.33

-

-

-

-

-

-

3800

1308

2.73

1381

2.93

1453

3.10

1525

3.25

1597

3.39

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZR102 (8.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

(CFM)

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

2 HP & Field

 

 

Standard 2 HP & Drive

 

 

 

 

Hi Static 3 HP & Drive

 

 

 

 

 

Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2200

715

0.72

768

0.85

818

0.98

867

1.09

914

1.21

960

1.32

1004

1.43

1047

1.53

1089

1.64

1131

1.75

2400

734

0.83

786

0.96

837

1.08

886

1.20

933

1.31

978

1.42

1022

1.53

1066

1.64

1108

1.75

1150

1.86

2600

755

0.95

808

1.08

858

1.20

907

1.32

954

1.44

1000

1.55

1044

1.65

1087

1.76

1129

1.87

1171

1.98

2800

779

1.09

832

1.22

882

1.35

931

1.46

978

1.58

1024

1.69

1068

1.80

1111

1.90

1153

2.01

1195

2.12

3000

806

1.25

859

1.38

910

1.51

958

1.63

1005

1.74

1051

1.85

1095

1.96

1138

2.07

1181

2.17

1222

2.28

3200

837

1.44

889

1.57

940

1.69

989

1.81

1036

1.93

1081

2.04

1125

2.14

1168

2.25

1211

2.36

1252

2.47

3400

870

1.65

922

1.78

973

1.90

1022

2.02

1069

2.13

1114

2.24

1158

2.35

1202

2.46

1244

2.57

1286

2.68

3600

906

1.88

959

2.01

1009

2.13

1058

2.25

1105

2.36

1150

2.47

1195

2.58

1238

2.69

1280

2.80

1322

2.91

3800

945

2.13

998

2.26

1048

2.38

1097

2.50

1144

2.61

1190

2.72

1234

2.83

1277

2.94

1319

3.05

1361

3.16

4000

987

2.40

1040

2.53

1090

2.66

1139

2.78

1186

2.89

1231

3.00

1276

3.11

1319

3.21

1361

3.32

1403

3.43

4200

1032

2.70

1084

2.83

1135

2.95

1184

3.07

1231

3.18

1276

3.29

1320

3.40

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

120

Johnson Controls Unitary Products

Page 120
Image 120
York R-410A ZH/ZJ/ZR Series manual ZR078-150Bottom Duct Application, ZR078 6.5 Ton Bottom Duct, ZR090 7.5 Ton Bottom Duct