York R-410A ZH/ZJ/ZR Series manual ZJ049 4.0 Ton Continued, Johnson Controls Unitary Products

Models: R-410A ZH/ZJ/ZR Series

1 206
Download 206 pages 7.86 Kb
Page 54
Image 54
ZJ049 (4.0 Ton) (Continued)

528150-YTG-G-1210

ZJ049 (4.0 Ton) (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

45.6

4.3

17.0

15.2

10.8

-

-

-

40.4

4.7

17.9

11.7

9.0

-

-

-

1000

 

72

40.1

4.2

25.9

21.5

17.1

12.8

-

-

35.0

4.6

23.8

19.5

15.2

10.9

-

-

 

67

34.7

4.1

34.7

27.8

23.4

19.1

14.7

-

29.7

4.4

29.7

26.4

21.4

17.1

12.8

-

 

 

 

 

62

29.8

4.2

29.8

29.8

27.1

22.7

18.4

14.0

24.8

4.5

24.8

24.8

24.8

19.2

14.9

10.6

 

 

77

47.2

4.3

22.6

17.1

12.1

-

-

-

41.7

4.7

23.3

15.1

10.1

-

-

-

 

 

72

41.5

4.2

29.3

24.2

19.2

14.1

-

-

36.1

4.6

27.0

22.0

17.1

12.1

-

-

1200

 

67

35.9

4.1

35.9

31.3

26.2

21.2

16.1

-

30.6

4.4

30.6

29.0

24.0

19.1

14.1

-

 

 

62

30.8

4.2

30.8

30.8

30.3

25.3

20.2

15.2

25.6

4.5

25.6

25.6

25.6

21.5

16.5

11.6

 

 

57

33.1

4.0

33.1

33.1

29.9

24.8

19.8

14.7

29.5

4.3

29.5

29.5

26.3

21.4

16.5

11.5

 

 

77

48.8

4.3

28.2

19.1

13.4

-

-

-

42.9

4.7

28.8

18.4

11.3

-

-

-

 

 

72

42.9

4.2

32.7

26.9

21.2

15.5

-

-

37.2

4.6

30.2

24.6

19.0

13.4

-

-

1400

 

67

37.1

4.1

37.1

34.8

29.0

23.3

17.6

-

31.6

4.4

31.6

31.6

26.7

21.1

15.5

-

 

 

62

31.9

4.2

31.9

31.9

33.6

27.8

22.1

16.3

26.4

4.5

26.4

26.4

26.4

23.8

18.2

12.6

 

 

57

34.2

4.0

34.2

34.2

33.1

27.3

21.6

15.9

30.4

4.3

30.4

30.4

29.3

23.7

18.1

12.5

 

 

77

50.4

4.3

33.8

21.1

14.7

-

-

-

44.2

4.7

34.2

21.8

12.4

-

-

-

 

 

72

44.3

4.2

36.1

29.7

23.2

16.8

-

-

38.4

4.6

33.4

27.1

20.9

14.6

-

-

1600

 

67

38.3

4.1

38.3

38.2

31.8

25.4

19.0

-

32.5

4.4

32.5

32.5

29.4

23.1

16.9

-

 

 

62

32.9

4.2

32.9

32.9

36.8

30.4

23.9

17.5

27.2

4.5

27.2

27.2

27.2

26.1

19.8

13.6

 

 

57

35.4

4.0

35.4

35.4

36.2

29.8

23.4

17.0

31.3

4.3

31.3

31.3

31.3

26.0

19.7

13.5

 

 

72

45.2

4.2

39.2

32.0

24.8

17.7

-

-

39.1

4.6

36.4

29.4

22.4

15.4

-

-

1800

 

67

39.0

4.1

39.0

39.0

34.0

26.8

19.7

-

33.1

4.4

33.1

33.1

31.5

24.5

17.5

-

 

62

33.5

4.2

33.5

33.5

35.5

28.3

21.1

14.0

27.7

4.5

27.7

27.7

27.7

23.3

16.3

9.3

 

 

 

 

57

36.0

4.0

36.0

36.0

36.5

29.3

22.1

15.0

31.9

4.3

31.9

31.9

31.9

25.4

18.4

11.4

 

 

72

46.0

4.2

42.2

34.3

26.4

18.5

-

-

39.8

4.5

39.4

31.6

23.9

16.1

-

-

2000

 

67

39.7

4.1

39.7

39.7

36.2

28.3

20.3

-

33.7

4.4

33.7

33.7

33.6

25.8

18.1

-

 

62

34.1

4.2

34.1

34.1

34.1

26.2

18.3

10.4

28.2

4.5

28.2

28.2

28.2

20.5

12.7

5.0

 

 

 

 

57

36.7

4.0

36.7

36.7

36.7

28.8

20.9

12.9

32.5

4.3

32.5

32.5

32.5

24.8

17.1

9.3

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

54

Johnson Controls Unitary Products

Page 54
Image 54
York R-410A ZH/ZJ/ZR Series manual ZJ049 4.0 Ton Continued, Johnson Controls Unitary Products