ZJ037-150 Side Duct Application

528150-YTG-G-1210

ZJ037-150 Side Duct Application

ZJ037 (3.0 Ton) Side Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

Hi Static 1.5 HP & Drive

 

 

 

 

 

 

900

560

0.29

628

0.35

695

0.42

760

0.51

823

0.61

886

0.72

949

0.82

1011

0.92

1073

1.01

1136

1.09

1000

582

0.29

650

0.34

716

0.42

781

0.51

845

0.61

908

0.71

970

0.82

1032

0.92

1095

1.01

1158

1.08

1100

601

0.30

670

0.35

736

0.43

801

0.52

864

0.62

927

0.72

990

0.83

1052

0.93

1114

1.02

1177

1.09

1200

620

0.32

688

0.37

754

0.45

819

0.54

883

0.64

946

0.74

1008

0.85

1070

0.95

1133

1.04

1196

1.11

1300

638

0.35

706

0.40

772

0.48

837

0.57

901

0.67

964

0.77

1026

0.88

1088

0.98

1151

1.06

1214

1.14

1400

655

0.39

724

0.44

790

0.51

855

0.60

918

0.70

981

0.81

1044

0.91

1106

1.01

1168

1.10

1231

1.18

1500

673

0.43

741

0.48

807

0.56

872

0.65

936

0.75

999

0.85

1061

0.96

1124

1.06

1186

1.15

1249

1.22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5 HP & Field Supplied Drive

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZJ049 (4.0 Ton) Side Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

FS4

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

Hi Static 1.5 HP & Drive

 

 

1200

608

0.25

677

0.34

744

0.44

807

0.54

868

0.64

927

0.74

986

0.84

1043

0.93

1101

1.02

1160

1.10

1300

623

0.28

692

0.37

758

0.47

822

0.57

883

0.67

942

0.77

1001

0.86

1058

0.96

1116

1.04

1175

1.13

1400

637

0.31

706

0.40

772

0.50

836

0.60

897

0.70

956

0.80

1015

0.90

1072

0.99

1130

1.08

1189

1.16

1500

650

0.35

720

0.44

786

0.54

849

0.64

911

0.74

970

0.84

1028

0.93

1086

1.03

1144

1.12

1202

1.20

1600

664

0.39

734

0.49

800

0.58

863

0.68

924

0.78

984

0.88

1042

0.98

1100

1.07

1158

1.16

1216

1.24

1700

678

0.44

748

0.54

814

0.63

877

0.73

938

0.83

998

0.93

1056

1.03

1114

1.12

1172

1.21

1230

1.29

1800

693

0.50

763

0.59

829

0.69

892

0.79

953

0.89

1013

0.99

1071

1.08

1129

1.18

1186

1.26

1245

1.35

1900

708

0.56

778

0.65

844

0.75

907

0.85

968

0.95

1028

1.05

1086

1.15

1144

1.24

1202

1.33

1260

1.41

2000

725

0.62

794

0.72

860

0.82

924

0.92

985

1.02

1044

1.12

1102

1.21

1160

1.30

1218

1.39

1277

1.47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive

ZJ061 (5.0 Ton) Side Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

 

0.4

0.6

 

0.8

1.0

1.2

1.4

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

RPM BHP

RPM BHP

RPM BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

1.5 HP & Field Suplied Drive

 

 

 

Standard 1.5 HP & Drive

 

 

 

Hi Static 2 HP & Drive

 

1500

659

0.35

719

0.46

780

0.57

843

0.67

905

0.77

964

0.87

1020

0.97

1071

1.07

1116

1.17

1154

1.28

1600

675

0.38

735

0.50

796

0.60

859

0.71

920

0.81

980

0.91

1036

1.01

1087

1.11

1132

1.21

1170

1.32

1700

691

0.42

751

0.54

812

0.64

875

0.75

936

0.85

996

0.95

1052

1.05

1103

1.15

1148

1.25

1186

1.36

1800

707

0.47

767

0.58

829

0.69

891

0.79

953

0.90

1012

0.99

1069

1.09

1120

1.20

1165

1.30

1202

1.41

1900

724

0.53

784

0.64

846

0.75

908

0.85

970

0.95

1029

1.05

1085

1.15

1137

1.25

1182

1.35

1219

1.46

2000

741

0.59

801

0.70

863

0.81

925

0.91

987

1.01

1047

1.11

1103

1.21

1154

1.31

1199

1.41

1236

1.52

2100

759

0.65

819

0.77

881

0.87

943

0.98

1005

1.08

1065

1.18

1121

1.28

1172

1.38

1217

1.48

1254

1.59

2200

778

0.73

838

0.84

900

0.95

962

1.05

1024

1.15

1083

1.25

1139

1.35

1191

1.45

1236

1.56

1273

1.66

2300

797

0.81

857

0.92

919

1.03

981

1.13

1043

1.23

1103

1.33

1159

1.43

1210

1.53

1255

1.64

1292

1.74

2400

817

0.90

877

1.01

939

1.12

1002

1.22

1063

1.32

1123

1.42

1179

1.52

1230

1.62

1275

1.73

1312

1.83

2500

838

1.00

898

1.11

960

1.22

1022

1.32

1084

1.42

1144

1.52

1200

1.62

1251

1.72

1296

1.82

1333

1.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS4

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Suppied Drive.

110

Johnson Controls Unitary Products

Page 110
Image 110
York R-410A ZH/ZJ/ZR Series manual ZJ037-150Side Duct Application, ZJ037 3.0 Ton Side Duct, ZJ049 4.0 Ton Side Duct