Manual background

 

 

 

 

 

 

 

 

 

 

528150-YTG-G-1210

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive

 

 

 

TEST CONFIGURATION

 

 

 

Horizontal (Side Return) Ducted Inlet

 

 

 

 

Indoor Blower Speed (RPM)

1,012- 5.5 Turns Open Equivalent

 

1,134 - 3 Turns Open Equivalent

 

1,174 - 2 Turns Open Equivalent

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

1.0

 

 

1.6

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

Nominal Airflow (CFM)

 

2,000

 

 

1,800

 

 

1,600

 

 

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

1.04

 

 

1.25

 

 

1.39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

 

ID Blower

 

Cooling

 

ID Blower

 

Cooling

 

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

 

 

 

 

 

 

 

63

76

 

78

 

78

 

79

 

79

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

125

70

 

73

 

73

 

76

 

74

 

77

 

 

 

 

 

 

 

 

 

 

 

 

 

250

68

 

70

 

68

 

69

 

69

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

500

61

 

62

 

61

 

62

 

60

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

61

 

62

 

61

 

62

 

58

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

57

 

58

 

57

 

58

 

54

 

56

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

56

 

56

 

55

 

56

 

52

 

53

 

 

 

 

 

 

 

 

 

 

 

 

 

8000

50

 

50

 

50

 

50

 

47

 

48

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Indoor Sound Power Levels (Horizontal Ducted Discharge, High Static Belt Drive)

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

Horizontal (Side Supply) Ducted Discharge

 

 

Indoor Blower Speed (RPM)

896 - 3.5 Turns Open Equivalent

1,072 - Fully Closed Equivalent

1,170 - 2.5 Turns Open Equivalent1

External Static Pressure (IWG)

 

1.0

 

1.6

 

2.0 1

Nominal Airflow (CFM)

 

1,200

 

1,100

 

1,000

 

 

 

 

 

 

 

Blower Motor BHP

 

0.64

 

0.93

 

1.08

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

ID Blower

 

Cooling

ID Blower

 

Cooling

Only (dB)

 

Operation2 (dB)

Only (dB)

 

Operation2 (dB)

Only (dB)

 

Operation2 (dB)

 

 

 

 

63

77

 

81

83

 

84

83

 

84

 

 

 

 

 

 

 

 

 

 

125

74

 

76

76

 

77

80

 

80

 

 

 

 

 

 

 

 

 

 

250

67

 

68

70

 

70

72

 

73

 

 

 

 

 

 

 

 

 

 

500

65

 

66

67

 

67

67

 

68

 

 

 

 

 

 

 

 

 

 

1000

61

 

62

67

 

67

66

 

69

 

 

 

 

 

 

 

 

 

 

2000

58

 

60

63

 

63

63

 

64

 

 

 

 

 

 

 

 

 

 

4000

57

 

59

62

 

62

62

 

63

 

 

 

 

 

 

 

 

 

 

8000

51

 

53

56

 

57

56

 

58

 

 

 

 

 

 

 

 

 

 

1.Requires driven pulley #AK-56, normal high static pulley is an #AK-69.

2.Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.