York R-410A ZH/ZJ/ZR Series manual Sound Performance, Indoor Sound Power Levels 3 thru 5 Ton

Models: R-410A ZH/ZJ/ZR Series

1 206
Download 206 pages 7.86 Kb
Page 122
Image 122
Sound Performance

528150-YTG-G-1210

Sound Performance

Indoor Sound Power Levels (3 thru 5 Ton)

Indoor Sound Power Levels (Horizontal Ducted Inlet, Standard Static Belt Drive)

UNIT DESCRIPTION / MODEL

 

ZH/ZJ/ZR037 / 3 Ton / Standard Static Belt Drive

 

TEST CONFIGURATION

 

Horizontal (Side Return) Ducted Inlet

 

Indoor Blower Speed (RPM)

612 - 3 Turns Open Equivalent

709 - 1 Turn Open Equivalent

External Static Pressure (IWG)

 

0.5

 

0.4

Airflow (CFM)

 

850

 

1300

Blower Motor BHP

 

0.37

 

0.40

Octave Center Freq. Hz

ID Blower Only (dB)

Cooling Operation1 (dB)

ID Blower Only (dB)

Cooling Operation1 (dB)

63

73

77

73

77

125

61

70

66

71

250

56

63

60

64

500

51

56

55

57

1000

44

48

51

52

2000

41

44

48

49

4000

44

47

47

48

8000

42

44

43

44

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL

 

ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive

 

TEST CONFIGURATION

 

Horizontal (Side Return) Ducted Inlet

 

Indoor Blower Speed (RPM)

612 - 3 Turns Open Equivalent

709 - 1 Turn Open Equivalent

External Static Pressure (IWG)

 

0.5

 

0.4

Airflow (CFM)

 

850

 

1300

Blower Motor BHP

 

0.37

 

0.40

Octave Center Freq. Hz

ID Blower Only (dB)

Cooling Operation1 (dB)

ID Blower Only (dB)

Cooling Operation1 (dB)

63

73

77

73

77

125

61

70

66

71

250

56

63

60

64

500

51

56

55

57

1000

44

48

51

52

2000

41

44

48

49

4000

44

47

47

48

8000

42

44

43

44

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

122

Johnson Controls Unitary Products