ZR078-150 Side Duct Application

ZR078 (6.5 Ton) Side Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

 

0.6

 

0.8

1.0

1.2

 

1.4

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

RPM BHP

RPM BHP

RPM BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

1.5 HP & Field Supplied Drive

 

 

 

Standard 1.5 HP & Drive

 

 

 

Hi Static 2 HP & Drive

 

1800

778

0.37

838

0.56

895

0.73

951

0.88

1005

1.01

1059

1.13

1112

1.25

1166

1.36

1221

1.47

1278

1.59

2000

803

0.50

864

0.69

921

0.85

977

1.00

1031

1.14

1085

1.26

1138

1.37

1192

1.49

1247

1.60

1304

1.72

2200

833

0.64

893

0.83

951

1.00

1006

1.14

1061

1.28

1114

1.40

1168

1.51

1221

1.63

1276

1.74

1333

1.86

2400

866

0.80

926

0.99

984

1.15

1039

1.30

1094

1.43

1147

1.56

1201

1.67

1254

1.78

1309

1.90

1366

2.02

2600

902

0.97

962

1.16

1020

1.33

1076

1.47

1130

1.61

1183

1.73

1237

1.85

1291

1.96

1346

2.07

1402

2.19

2800

941

1.16

1002

1.35

1059

1.52

1115

1.67

1169

1.80

1222

1.92

1276

2.04

1330

2.15

1385

2.26

-

-

3000

983

1.37

1043

1.56

1101

1.73

1157

1.88

1211

2.01

1264

2.13

1318

2.25

-

-

-

-

-

-

3200

1028

1.60

1088

1.79

1145

1.95

1201

2.10

1255

2.24

-

-

-

-

-

-

-

-

-

-

3400

1074

1.84

1134

2.03

1192

2.20

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 HP & Field Supplied Drive

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZR090 (7.5 Ton) Side Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

1.5 HP & Field Supplied Drive

 

 

Standard 1.5 HP & Drive

 

 

 

 

Hi Static 3 HP & Drive

 

 

2000

803

0.50

864

0.69

921

0.85

977

1.00

1031

1.14

1085

1.26

1138

1.37

1192

1.49

1247

1.60

1304

1.72

2200

833

0.64

893

0.83

951

1.00

1006

1.14

1061

1.28

1114

1.40

1168

1.51

1221

1.63

1276

1.74

1333

1.86

2400

866

0.80

926

0.99

984

1.15

1039

1.30

1094

1.43

1147

1.56

1201

1.67

1254

1.78

1309

1.90

1366

2.02

2600

902

0.97

962

1.16

1020

1.33

1076

1.47

1130

1.61

1183

1.73

1237

1.85

1291

1.96

1346

2.07

1402

2.19

2800

941

1.16

1002

1.35

1059

1.52

1115

1.67

1169

1.80

1222

1.92

1276

2.04

1330

2.15

1385

2.26

1442

2.38

3000

983

1.37

1043

1.56

1101

1.73

1157

1.88

1211

2.01

1264

2.13

1318

2.25

1372

2.36

1427

2.47

1483

2.59

3200

1028

1.60

1088

1.79

1145

1.95

1201

2.10

1255

2.24

1309

2.36

1362

2.47

1416

2.59

1471

2.70

1528

2.82

3400

1074

1.84

1134

2.03

1192

2.20

1248

2.35

1302

2.48

1355

2.60

1409

2.72

1463

2.83

1518

2.94

1574

3.06

3600

1123

2.10

1183

2.29

1241

2.46

1297

2.61

1351

2.74

1404

2.86

1458

2.98

1512

3.09

1567

3.21

1623

3.32

3800

1174

2.38

1234

2.57

1292

2.74

1348

2.88

1402

3.02

1455

3.14

1509

3.26

1562

3.37

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZR102 (8.5 Ton) Side Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

2 HP & Field

 

 

 

Standard 2 HP & Drive

 

 

 

 

 

Hi Static 3 HP & Drive

 

 

 

Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2200

684

0.48

735

0.67

783

0.84

829

1.01

874

1.17

918

1.32

960

1.48

1001

1.63

1041

1.78

1081

1.94

2400

695

0.58

745

0.76

793

0.94

840

1.11

885

1.27

928

1.42

970

1.57

1011

1.73

1052

1.88

1091

2.04

2600

706

0.67

756

0.86

805

1.04

851

1.20

896

1.36

939

1.52

981

1.67

1023

1.82

1063

1.98

1103

2.13

2800

719

0.78

769

0.96

817

1.14

863

1.31

908

1.47

952

1.62

994

1.78

1035

1.93

1075

2.08

1115

2.24

3000

732

0.89

782

1.08

831

1.25

877

1.42

922

1.58

965

1.74

1007

1.89

1049

2.04

1089

2.19

1128

2.35

3200

747

1.02

797

1.21

846

1.38

892

1.55

937

1.71

980

1.86

1023

2.02

1064

2.17

1104

2.32

1144

2.48

3400

764

1.16

814

1.35

862

1.53

909

1.69

954

1.85

997

2.01

1039

2.16

1080

2.31

1121

2.47

1160

2.62

3600

783

1.33

833

1.51

881

1.69

927

1.86

972

2.02

1016

2.17

1058

2.32

1099

2.48

1139

2.63

1179

2.79

3800

803

1.51

853

1.69

901

1.87

948

2.04

992

2.20

1036

2.35

1078

2.50

1119

2.66

1159

2.81

1199

2.97

4000

825

1.71

875

1.89

923

2.07

970

2.23

1014

2.39

1058

2.55

1100

2.70

1141

2.86

1181

3.01

1221

3.16

4200

849

1.92

899

2.11

947

2.29

993

2.45

1038

2.61

1082

2.77

1124

2.92

1165

3.07

1205

3.23

1245

3.38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

Johnson Controls Unitary Products

117

Page 117
Image 117
York R-410A ZH/ZJ/ZR Series manual ZR078-150Side Duct Application, ZR078 6.5 Ton Side Duct, ZR090 7.5 Ton Side Duct