Manual background

528150-YTG-G-1210

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

Horizontal (Side Supply) Ducted Discharge

 

 

Indoor Blower Speed (RPM)

922 - 6 Turns Open Equivalent

1,069 - 4 Turns Open Equivalent

1,165 - 2.5 Turns Open Equivalent

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

1.0

 

1.6

 

2.0

 

 

 

 

 

 

 

Nominal Airflow (CFM)

 

1,600

 

1,400

 

1,200

 

 

 

 

 

 

 

Blower Motor BHP

 

0.86

 

1.03

 

1.13

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

ID Blower

 

Cooling

ID Blower

 

Cooling

Only (dB)

 

Operation1 (dB)

Only (dB)

 

Operation1 (dB)

Only (dB)

 

Operation1 (dB)

 

 

 

 

63

80

 

82

82

 

83

84

 

84

 

 

 

 

 

 

 

 

 

 

125

76

 

77

76

 

77

78

 

79

 

 

 

 

 

 

 

 

 

 

250

71

 

72

72

 

72

74

 

74

 

 

 

 

 

 

 

 

 

 

500

69

 

69

69

 

69

70

 

70

 

 

 

 

 

 

 

 

 

 

1000

65

 

65

69

 

69

70

 

70

 

 

 

 

 

 

 

 

 

 

2000

64

 

64

64

 

64

65

 

65

 

 

 

 

 

 

 

 

 

 

4000

63

 

63

63

 

63

64

 

64

 

 

 

 

 

 

 

 

 

 

8000

58

 

58

58

 

58

59

 

59

 

 

 

 

 

 

 

 

 

 

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

Horizontal (Side Supply) Ducted Discharge

 

 

Indoor Blower Speed (RPM)

1,009- 5.5 Turns Open Equivalent

1,131 - 3 Turns Open Equivalent

1,184 - 2 Turns Open Equivalent

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

1.0

 

1.6

 

2.0

 

 

 

 

 

 

 

Nominal Airflow (CFM)

 

2,000

 

1,800

 

1,600

 

 

 

 

 

 

 

Blower Motor BHP

 

1.04

 

1.25

 

1.39

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

ID Blower

 

Cooling

ID Blower

 

Cooling

Only (dB)

 

Operation1 (dB)

Only (dB)

 

Operation1 (dB)

Only (dB)

 

Operation1 (dB)

 

 

 

 

63

84

 

85

82

 

83

82

 

83

 

 

 

 

 

 

 

 

 

 

125

78

 

79

79

 

79

78

 

79

 

 

 

 

 

 

 

 

 

 

250

75

 

75

74

 

75

73

 

73

 

 

 

 

 

 

 

 

 

 

500

71

 

71

70

 

71

69

 

69

 

 

 

 

 

 

 

 

 

 

1000

69

 

69

71

 

71

71

 

72

 

 

 

 

 

 

 

 

 

 

2000

66

 

67

67

 

67

66

 

66

 

 

 

 

 

 

 

 

 

 

4000

66

 

66

66

 

67

66

 

66

 

 

 

 

 

 

 

 

 

 

8000

61

 

62

61

 

62

60

 

60

 

 

 

 

 

 

 

 

 

 

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

130

Johnson Controls Unitary Products

Page 130
Image 130
York R-410A ZH/ZJ/ZR Series manual Indoor Blower Speed RPM