ZJ037-150 Bottom Duct Application

528150-YTG-G-1210

ZJ037-150 Bottom Duct Application

ZJ037 (3.0 Ton) Bottom Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

Standard 1.5 HP & Drive

 

 

 

 

Hi Static 1.5 HP & Drive

 

 

 

 

 

 

 

900

605

0.23

671

0.33

738

0.42

804

0.52

869

0.62

933

0.71

995

0.80

1054

0.89

1111

0.98

1164

1.07

1000

621

0.25

688

0.34

754

0.44

820

0.53

885

0.63

949

0.72

1011

0.82

1071

0.91

1127

1.00

1180

1.09

1100

637

0.27

703

0.36

769

0.46

835

0.56

900

0.65

964

0.74

1026

0.84

1086

0.93

1142

1.02

1195

1.11

1200

651

0.30

717

0.39

784

0.49

850

0.58

915

0.68

979

0.77

1041

0.87

1100

0.96

1157

1.05

1210

1.13

1300

666

0.33

732

0.43

799

0.52

865

0.62

930

0.71

994

0.81

1056

0.90

1115

0.99

1172

1.08

1225

1.17

1400

681

0.37

747

0.47

814

0.56

880

0.66

945

0.75

1009

0.85

1071

0.94

1130

1.03

1187

1.12

1240

1.21

1500

697

0.42

763

0.51

830

0.61

896

0.71

961

0.80

1025

0.90

1087

0.99

1146

1.08

1203

1.17

1256

1.26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5 HP & Field Supplied Drive

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZJ049 (4.0 Ton) Bottom Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

FS4

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

Hi Static 1.5 HP & Drive

 

 

1200

635

0.25

704

0.34

770

0.44

832

0.54

893

0.65

953

0.75

1013

0.85

1073

0.94

1134

1.02

1197

1.08

1300

648

0.28

717

0.38

782

0.47

845

0.58

906

0.68

966

0.78

1025

0.88

1085

0.97

1147

1.05

1210

1.12

1400

661

0.32

730

0.42

796

0.51

858

0.62

919

0.72

979

0.82

1039

0.92

1099

1.01

1160

1.09

1223

1.16

1500

675

0.37

744

0.46

810

0.56

872

0.66

933

0.77

993

0.87

1053

0.96

1113

1.05

1174

1.14

1237

1.20

1600

690

0.42

759

0.51

825

0.61

887

0.72

948

0.82

1008

0.92

1068

1.02

1128

1.11

1189

1.19

1252

1.26

1700

706

0.48

775

0.57

841

0.67

903

0.77

964

0.88

1024

0.98

1084

1.08

1144

1.17

1205

1.25

1268

1.31

1800

723

0.55

792

0.64

857

0.74

920

0.84

981

0.94

1041

1.04

1101

1.14

1161

1.23

1222

1.31

1285

1.38

1900

741

0.62

810

0.71

875

0.81

938

0.91

999

1.01

1059

1.11

1118

1.21

1178

1.30

1240

1.38

1303

1.45

2000

760

0.69

829

0.79

894

0.88

957

0.99

1018

1.09

1078

1.19

1137

1.29

1197

1.38

1258

1.46

1322

1.53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

ZJ061 (5.0 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

 

1.8

2.0

(CFM)

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM

BHP

RPM

BHP

 

 

1.5 HP & Field Supplied Drive

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

Hi Static 2 HP & Drive

 

1500

673

0.47

736

0.54

797

0.63

855

0.72

910

0.82

964

0.92

1016

1.03

1067

1.14

1117

1.25

1166

1.36

1600

693

0.49

756

0.57

817

0.65

874

0.75

930

0.85

984

0.95

1036

1.06

1087

1.17

1137

1.28

1186

1.39

1700

713

0.53

777

0.60

837

0.69

895

0.78

951

0.88

1004

0.98

1057

1.09

1107

1.20

1157

1.31

1207

1.42

1800

734

0.57

797

0.65

858

0.73

916

0.83

971

0.92

1025

1.03

1077

1.14

1128

1.25

1178

1.36

1228

1.47

1900

755

0.62

819

0.70

879

0.79

937

0.88

992

0.98

1046

1.08

1098

1.19

1149

1.30

1199

1.41

1249

1.52

2000

776

0.69

840

0.76

900

0.85

958

0.94

1014

1.04

1067

1.14

1120

1.25

1171

1.36

1221

1.47

1270

1.59

2100

798

0.76

861

0.84

921

0.92

979

1.02

1035

1.11

1089

1.22

1141

1.32

1192

1.44

1242

1.55

1291

1.66

2200

819

0.84

882

0.92

943

1.00

1001

1.10

1056

1.20

1110

1.30

1162

1.41

1213

1.52

1263

1.63

1312

1.74

2300

840

0.93

903

1.01

964

1.10

1022

1.19

1077

1.29

1131

1.39

1183

1.50

1234

1.61

1284

1.72

1334

1.83

2400

861

1.03

925

1.11

985

1.20

1043

1.29

1099

1.39

1152

1.49

1204

1.60

1255

1.71

1305

1.82

1355

1.93

2500

882

1.14

946

1.22

1006

1.30

1064

1.40

1120

1.50

1173

1.60

1226

1.71

1276

1.82

1326

1.93

1376

2.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 HP & Field Supplied Drive

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

Johnson Controls Unitary Products

113

Page 113
Image 113
York R-410A ZH/ZJ/ZR Series manual ZJ037-150Bottom Duct Application, ZJ037 3.0 Ton Bottom Duct, ZJ049 4.0 Ton Bottom Duct