Indoor Sound Power Levels (Vertical Ducted Inlet, High Static Belt Drive)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive

 

 

 

 

TEST CONFIGURATION

 

 

 

Vertical (Bottom Return) Ducted Inlet

 

 

 

 

 

Indoor Blower Speed (RPM)

927 - 3 Turns Open Equivalent

 

1,085 - 1/2 Turn Open Equivalent

 

1,190 - 2.5 Turns Open Equivalent1

 

 

External Static Pressure (IWG)

 

1.0

 

 

1.6

 

 

2.01

 

 

Nominal Airflow (CFM)

 

1,200

 

 

1,100

 

 

1,000

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

0.68

 

 

0.93

 

 

1.09

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

 

ID Blower

 

Cooling

 

ID Blower

 

Cooling

 

Only (dB)

 

Operation2 (dB)

 

Only (dB)

 

Operation2 (dB)

 

Only (dB)

 

Operation2 (dB)

 

 

 

 

 

 

 

 

63

77

 

79

 

82

 

83

 

79

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125

68

 

69

 

70

 

71

 

72

 

73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

60

 

67

 

62

 

69

 

64

 

67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

58

 

58

 

63

 

63

 

62

 

63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

54

 

55

 

60

 

60

 

60

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

48

 

49

 

56

 

56

 

55

 

55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

43

 

44

 

48

 

49

 

51

 

51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8000

44

 

44

 

45

 

46

 

47

 

47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Requires driven pulley #AK-56, normal high static pulley is an #AK-69.

2.Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

 

Vertical (Bottom Return) Ducted Inlet

 

 

 

Indoor Blower Speed (RPM)

968 - 5.5 Turns Open Equivalent

 

1,120 - 3.5 Turns Open Equivalent

 

1,218 - 2.0 Turns Open Equivalent

 

 

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

1.0

 

 

1.6

 

 

2.0

 

 

 

 

 

 

 

 

 

Nominal Airflow (CFM)

 

1,600

 

 

1,400

 

 

1,200

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

0.86

 

 

1.03

 

 

1.13

 

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

 

ID Blower

 

Cooling

 

ID Blower

 

Cooling

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

 

 

 

 

 

63

77

 

79

 

78

 

78

 

81

 

81

 

 

 

 

 

 

 

 

 

 

 

 

125

69

 

73

 

71

 

73

 

73

 

74

 

 

 

 

 

 

 

 

 

 

 

 

250

63

 

63

 

63

 

64

 

66

 

66

 

 

 

 

 

 

 

 

 

 

 

 

500

63

 

64

 

62

 

63

 

64

 

64

 

 

 

 

 

 

 

 

 

 

 

 

1000

59

 

59

 

59

 

59

 

61

 

61

 

 

 

 

 

 

 

 

 

 

 

 

2000

54

 

54

 

53

 

54

 

56

 

56

 

 

 

 

 

 

 

 

 

 

 

 

4000

49

 

49

 

48

 

48

 

50

 

51

 

 

 

 

 

 

 

 

 

 

 

 

8000

45

 

46

 

45

 

46

 

47

 

47

 

 

 

 

 

 

 

 

 

 

 

 

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.