ZJ078 (6.5 Ton) Bottom Duct

528150-YTG-G-1210

ZJ078 (6.5 Ton) Bottom Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

FS4

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

Hi Static 2 HP & Drive

 

 

 

1800

603

0.13

656

0.36

718

0.58

784

0.79

851

0.98

914

1.16

968

1.31

1010

1.43

1035

1.53

1039

1.59

2000

627

0.26

680

0.49

742

0.71

808

0.92

875

1.12

937

1.29

992

1.44

1034

1.57

1059

1.66

1063

1.72

2200

650

0.40

703

0.63

765

0.85

831

1.06

898

1.25

961

1.43

1015

1.58

1057

1.71

1082

1.80

1086

1.86

2400

673

0.55

726

0.78

788

1.00

854

1.21

921

1.40

984

1.58

1038

1.73

1080

1.85

1105

1.95

1109

2.01

2600

696

0.71

749

0.94

811

1.16

878

1.37

944

1.56

1007

1.73

1061

1.89

1103

2.01

1128

2.10

1133

2.16

2800

720

0.87

773

1.10

835

1.32

902

1.53

968

1.73

1031

1.90

1085

2.05

1127

2.18

1152

2.27

1157

2.33

3000

745

1.05

798

1.28

860

1.50

926

1.71

993

1.91

1056

2.08

1110

2.23

1152

2.36

1177

2.45

1181

2.51

3200

771

1.24

824

1.47

886

1.69

952

1.90

1019

2.09

1081

2.27

1136

2.42

1178

2.54

1203

2.64

1207

2.70

3400

797

1.44

850

1.67

912

1.89

979

2.10

1045

2.29

1108

2.47

1162

2.62

1204

2.74

1229

2.84

1234

2.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

ZJ090 (7.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

 

0.8

1.0

1.2

1.4

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

RPM

BHP

RPM

BHP

RPM BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

 

 

FS4

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

Hi Static 3 HP & Drive

 

 

2000

644

0.11

698

0.38

755

0.62

814

0.85

874

1.06

933

1.26

990

1.46

1043

1.66

1090

1.87

1131

2.09

2200

666

0.26

720

0.53

777

0.77

836

1.00

896

1.21

956

1.41

1012

1.61

1065

1.81

1113

2.02

1153

2.24

2400

689

0.42

743

0.69

800

0.93

859

1.16

919

1.37

978

1.57

1035

1.77

1088

1.97

1135

2.18

1176

2.40

2600

712

0.60

766

0.87

823

1.11

882

1.34

942

1.55

1002

1.75

1058

1.95

1111

2.15

1159

2.36

1199

2.58

2800

736

0.80

790

1.06

847

1.31

906

1.53

967

1.74

1026

1.94

1082

2.14

1135

2.34

1183

2.55

1223

2.78

3000

761

1.00

815

1.27

872

1.52

931

1.74

991

1.95

1051

2.15

1107

2.35

1160

2.55

1208

2.76

1248

2.98

3200

787

1.22

840

1.49

898

1.74

957

1.96

1017

2.17

1076

2.37

1133

2.57

1186

2.77

1233

2.98

1274

3.20

3400

813

1.46

867

1.73

924

1.97

984

2.19

1044

2.40

1103

2.61

1160

2.80

1212

3.01

1260

3.21

-

-

3600

841

1.70

894

1.97

952

2.21

1011

2.44

1071

2.65

1130

2.85

1187

3.05

-

-

-

-

-

-

3800

869

1.96

923

2.22

980

2.47

1039

2.69

1099

2.90

1158

3.10

1215

3.30

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

ZJ102 (8.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

0.2

0.4

0.6

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

FS4

 

 

Standard 2 HP & Drive

 

 

 

 

 

Hi Static 3 HP & Drive

 

 

 

2200

685

0.59

739

0.74

791

0.88

841

1.01

889

1.14

936

1.27

981

1.39

1025

1.51

1069

1.63

1111

1.75

2400

702

0.70

756

0.85

808

0.99

858

1.12

906

1.25

953

1.37

999

1.49

1043

1.62

1086

1.74

1129

1.86

2600

722

0.83

776

0.97

828

1.11

878

1.25

926

1.37

973

1.50

1018

1.62

1063

1.74

1106

1.86

1149

1.99

2800

744

0.97

798

1.12

850

1.26

900

1.39

949

1.52

995

1.64

1041

1.76

1085

1.88

1128

2.00

1171

2.13

3000

769

1.13

823

1.28

875

1.42

925

1.55

974

1.68

1020

1.80

1066

1.92

1110

2.05

1153

2.17

1196

2.29

3200

797

1.32

851

1.46

903

1.60

953

1.74

1001

1.86

1048

1.99

1093

2.11

1138

2.23

1181

2.35

1224

2.48

3400

828

1.52

882

1.67

934

1.81

983

1.94

1032

2.07

1078

2.19

1124

2.32

1168

2.44

1212

2.56

1254

2.68

3600

861

1.75

915

1.90

967

2.04

1017

2.17

1065

2.30

1112

2.42

1157

2.54

1201

2.67

1245

2.79

1287

2.91

3800

897

2.00

951

2.15

1002

2.29

1052

2.42

1101

2.55

1147

2.67

1193

2.80

1237

2.92

1280

3.04

1323

3.16

4000

935

2.27

989

2.42

1041

2.56

1091

2.69

1139

2.82

1186

2.95

1231

3.07

1275

3.19

1319

3.31

1362

3.43

4200

976

2.57

1030

2.72

1082

2.86

1132

2.99

1180

3.12

1227

3.24

1272

3.36

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

114

Johnson Controls Unitary Products

Page 114
Image 114
York R-410A ZH/ZJ/ZR Series manual ZJ078 6.5 Ton Bottom Duct, ZJ090 7.5 Ton Bottom Duct, ZJ102 8.5 Ton Bottom Duct