Drive Selection

528150-YTG-G-1210

Drive Selection

1.Determine side or bottom supply duct Application.

2.Determine desired airflow.

3.Calculate or measure the amount of external static pressure.

Add or deduct any additional static resistance from “Additional Static Resistance Table”.

4.Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.)

5.Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.

6.Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.

7.Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.

8.Determine turns open to obtain the desired operation point.

Example

1.2600 CFM

2.1.6 iwg

3.Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.

4.Using the RPM selection table below, Size X and Model Y is found.

5.1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.

6.1268 RPM is within the range of the 2 HP drives.

7.Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.

Airflow Performance

Example Supply Air Blower Performance

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG

 

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

 

 

 

 

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

 

1.5 HP & Field Supplied Drive

 

 

 

Standard 1.5 HP & Drive

 

 

Alternate 2 HP & Drive

 

2200

804

0.50

866

0.71

925

0.90

982

1.06

1038

1.21

1092

1.35

1147

1.48

1203

1.61

1259

1.73

1317

1.87

2400

835

0.66

897

0.87

956

1.06

1013

1.22

1069

1.37

1124

1.51

1178

1.64

1234

1.77

1290

1.90

1348

2.03

2600

869

0.84

931

1.05

990

1.24

1047

1.40

1103

1.55

1158

1.69

1212

1.82

1268

1.95

1324

2.07

1382

2.21

2800

906

1.03

968

1.25

1027

1.43

1084

1.60

1139

1.75

1194

1.89

1249

2.02

1304

2.14

1361

2.27

-

-

Example RPM Selection

Size

Model

Airflow

HP

Max

Motor

Blower

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1 Turn

Fully

(Tons)

Option

BHP

Sheave

Sheave

Open

Open

Open

Open

Open

Open

Closed

 

 

X

Y

Std.

1.5

1.73

1VM50

AK74

N/A

897

945

991

1035

1079

1126

H. Static

2

2.30

1VM50

AK64

N/A

1039

1094

1150

1207

1256

1308

 

 

Example Additional Static Resistance

Size

Model

CFM

Cooling Only

Economizer

4” Pleated Filter

 

 

Electric Heat kW

 

 

(Tons)

3

6

9

15

20

24

 

 

 

 

 

 

 

900

0.05

-0.05

0.01

0.00

0.00

0.00

0.01

0.01

0.01

 

 

1000

0.05

-0.03

0.02

0.00

0.00

0.00

0.02

0.02

0.02

X

Y

1100

0.04

-0.02

0.03

0.01

0.01

0.01

0.02

0.02

0.02

 

 

1200

0.04

0.00

0.04

0.01

0.01

0.01

0.02

0.02

0.02

 

 

1300

0.03

0.01

0.05

0.01

0.01

0.01

0.03

0.03

0.03

96

Johnson Controls Unitary Products

Page 96
Image 96