Image 121
ZR120 (10 Ton) Bottom Duct

528150-YTG-G-1210

ZR120 (10 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

(CFM)

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

2 HP & Field

 

 

Standard 2 HP & Drive

 

 

 

Hi Static 3 HP & Drive

 

 

 

 

 

 

Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2600

755

0.95

808

1.08

858

1.20

907

1.32

954

1.44

1000

1.55

1044

1.65

1087

1.76

1129

1.87

1171

1.98

2800

779

1.09

832

1.22

882

1.35

931

1.46

978

1.58

1024

1.69

1068

1.80

1111

1.90

1153

2.01

1195

2.12

3000

806

1.25

859

1.38

910

1.51

958

1.63

1005

1.74

1051

1.85

1095

1.96

1138

2.07

1181

2.17

1222

2.28

3200

837

1.44

889

1.57

940

1.69

989

1.81

1036

1.93

1081

2.04

1125

2.14

1168

2.25

1211

2.36

1252

2.47

3400

870

1.65

922

1.78

973

1.90

1022

2.02

1069

2.13

1114

2.24

1158

2.35

1202

2.46

1244

2.57

1286

2.68

3600

906

1.88

959

2.01

1009

2.13

1058

2.25

1105

2.36

1150

2.47

1195

2.58

1238

2.69

1280

2.80

1322

2.91

3800

945

2.13

998

2.26

1048

2.38

1097

2.50

1144

2.61

1190

2.72

1234

2.83

1277

2.94

1319

3.05

1361

3.16

4000

987

2.40

1040

2.53

1090

2.66

1139

2.78

1186

2.89

1231

3.00

1276

3.11

1319

3.21

1361

3.32

1403

3.43

4200

1032

2.70

1084

2.83

1135

2.95

1184

3.07

1231

3.18

1276

3.29

1320

3.40

-

-

-

-

-

-

4400

1079

3.01

1132

3.15

1182

3.27

1231

3.39

-

-

-

-

-

-

-

-

-

-

-

-

4600

1129

3.35

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

ZR150 (12.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

(CFM)

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

3 HP & Field

 

 

 

Standard 3 HP & Drive

 

 

 

 

 

Hi Static 5 HP & Drive

 

 

 

Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3200

837

1.44

889

1.57

940

1.69

989

1.81

1036

1.93

1081

2.04

1125

2.14

1168

2.25

1211

2.36

1252

2.47

3400

870

1.65

922

1.78

973

1.90

1022

2.02

1069

2.13

1114

2.24

1158

2.35

1202

2.46

1244

2.57

1286

2.68

3600

906

1.88

959

2.01

1009

2.13

1058

2.25

1105

2.36

1150

2.47

1195

2.58

1238

2.69

1280

2.80

1322

2.91

3800

945

2.13

998

2.26

1048

2.38

1097

2.50

1144

2.61

1190

2.72

1234

2.83

1277

2.94

1319

3.05

1361

3.16

4000

987

2.40

1040

2.53

1090

2.66

1139

2.78

1186

2.89

1231

3.00

1276

3.11

1319

3.21

1361

3.32

1403

3.43

4200

1032

2.70

1084

2.83

1135

2.95

1184

3.07

1231

3.18

1276

3.29

1320

3.40

1364

3.51

1406

3.62

1447

3.73

4400

1079

3.01

1132

3.15

1182

3.27

1231

3.39

1278

3.50

1324

3.61

1368

3.72

1411

3.83

1453

3.93

1495

4.05

4600

1129

3.35

1182

3.48

1232

3.61

1281

3.72

1328

3.84

1374

3.95

1418

4.06

1461

4.16

1503

4.27

1545

4.38

4800

1182

3.71

1235

3.84

1285

3.96

1334

4.08

1381

4.20

1426

4.31

1471

4.41

1514

4.52

1556

4.63

1598

4.74

5000

1237

4.08

1290

4.22

1340

4.34

1389

4.46

1436

4.57

1481

4.68

1526

4.79

1569

4.90

1611

5.01

1653

5.12

5200

1294

4.48

1347

4.61

1398

4.74

1446

4.85

1493

4.97

1539

5.08

1583

5.19

1626

5.29

1669

5.40

1710

5.51

5400

1354

4.89

1407

5.03

1457

5.15

1506

5.27

1553

5.38

1599

5.49

1643

5.60

1686

5.71

-

-

-

-

5600

1416

5.33

1469

5.46

1519

5.58

1568

5.70

-

-

-

-

-

-

-

-

-

-

-

-

5800

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

5 HP & Field Supplied Drive

 

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

Johnson Controls Unitary Products

121

Page 121
Image 121
York R-410A ZH/ZJ/ZR Series manual YTG-G-1210, ZR120 10 Ton Bottom Duct, ZR150 12.5 Ton Bottom Duct