UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR049 / 4 Ton / Standard Static Belt Drive

 

 

 

 

TEST CONFIGURATION

 

 

Vertical (Bottom Supply) Ducted Discharge

 

 

 

 

 

 

 

 

 

Indoor Blower Speed (RPM)

609 - 3 Turns Open Equivalent

712 - 1 Turn Open Equivalent

 

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

0.4

 

0.6

 

 

 

 

 

 

 

 

 

Airflow (CFM)

 

850

 

950

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

0.32

 

0.42

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower Only (dB)

 

Cooling Operation1 (dB)

ID Blower Only (dB)

 

Cooling Operation1 (dB)

 

63

76

 

77

81

 

81

 

 

 

 

 

 

 

 

 

 

125

68

 

68

72

 

72

 

 

 

 

 

 

 

 

 

 

250

55

 

65

57

 

57

 

 

 

 

 

 

 

 

 

 

500

56

 

57

57

 

57

 

 

 

 

 

 

 

 

 

 

1000

51

 

57

52

 

56

 

 

 

 

 

 

 

 

 

 

2000

49

 

49

50

 

50

 

 

 

 

 

 

 

 

 

 

4000

48

 

48

49

 

51

 

 

 

 

 

 

 

 

 

 

8000

46

 

46

47

 

48

 

 

 

 

 

 

 

 

 

 

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL

 

ZH/ZJ/ZR061 / 5 Ton / Standard Static Belt Drive

 

TEST CONFIGURATION

 

Vertical (Bottom Supply) Ducted Discharge

 

Indoor Blower Speed (RPM)

809 - 3 Turns Open Equivalent

914 - 1 Turn Open Equivalent

External Static Pressure (IWG)

 

0.5

 

0.8

Airflow (CFM)

 

1700

 

1800

Blower Motor BHP

 

0.64

 

0.83

Octave Center Freq. Hz

ID Blower Only (dB)

Cooling Operation1 (dB)

ID Blower Only (dB)

Cooling Operation1 (dB)

63

81

81

79

79

125

75

75

75

76

250

65

65

63

63

500

67

67

67

67

1000

63

63

63

63

2000

61

62

61

61

4000

62

62

61

61

8000

57

57

56

56

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.