ZR049 (4.0 Ton) Reheat

528150-YTG-G-1210

ZR049 (4.0 Ton) Reheat

 

Air on

 

 

 

Temperature of Air on Condenser Coil

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

Total

 

Total

 

Sensible Capacity (MBh)

 

(- indicates heating)

 

 

(- indicates heating)

 

 

 

 

 

 

 

 

 

Capacity1

Input

 

 

Capacity1

 

Input

 

 

CFM

 

WB

(MBh)

(kW)2

 

Return Dry Bulb (°F)

(MBh)

 

(kW)2

 

Return Dry Bulb (°F)

 

(°F)

 

75

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 °F

 

 

 

 

50 °F

 

 

62.5

24.5

2.5

 

9.1

22.9

 

2.6

 

8.0

1200

 

64

25.7

2.5

 

7.4

26.9

 

2.7

 

7.2

 

 

65.3

26.6

2.5

 

6.1

27.1

 

2.6

 

5.5

 

 

62.5

24.0

2.5

 

12.4

24.5

 

2.6

 

11.2

1600

 

64

25.8

2.5

 

10.0

26.7

 

2.6

 

9.2

 

 

65.3

27.1

2.5

 

8.3

28.5

 

2.6

 

7.7

 

 

62.5

24.3

2.5

 

12.9

22.7

 

2.6

 

11.6

2000

 

64

26.2

2.5

 

11.1

24.7

 

2.6

 

10.0

 

 

65.3

27.1

2.5

 

9.2

26.5

 

2.6

 

8.5

 

 

 

 

 

60 °F

 

 

 

 

70 °F

 

 

62.5

21.8

2.6

 

7.1

19.8

 

2.7

 

6.2

1200

 

64

25.3

2.7

 

6.3

23.0

 

2.8

 

0.0

 

 

65.3

26.9

2.7

 

4.8

23.5

 

2.7

 

2.9

 

 

62.5

22.7

2.7

 

9.9

20.6

 

2.7

 

8.8

1600

 

64

25.4

2.7

 

8.8

22.4

 

2.8

 

6.8

 

 

65.3

26.9

2.7

 

7.5

24.4

 

2.8

 

5.9

 

 

62.5

20.1

2.6

 

10.2

18.2

 

2.7

 

8.9

2000

 

64

22.3

2.6

 

8.6

20.5

 

2.7

 

7.7

 

 

62

23.7

2.6

 

6.9

21.4

 

2.7

 

5.3

 

 

 

 

 

75 °F

 

 

 

 

80 °F

 

 

62.5

19.0

2.7

 

5.5

17.6

 

2.8

 

4.7

1200

 

64

21.5

2.8

 

5.1

20.9

 

2.9

 

3.7

 

 

65.3

22.2

2.8

 

2.8

21.5

 

2.9

 

2.3

 

 

62.5

19.3

2.8

 

8.1

17.9

 

2.9

 

7.5

1600

 

64

21.3

2.8

 

6.3

19.9

 

2.9

 

5.7

 

 

65.3

22.6

2.8

 

4.7

21.1

 

2.9

 

4.1

 

 

62.5

16.9

2.7

 

7.9

15.1

 

2.8

 

7.1

2000

 

64

18.2

2.7

 

6.3

16.7

 

2.8

 

5.6

 

 

65.3

19.9

2.8

 

4.8

18.3

 

2.8

 

4.0

 

 

 

 

 

85 °F

 

 

 

 

95 °F

 

 

62.5

17.7

2.9

 

5.0

12.8

 

3.1

 

3.5

1200

 

64

19.0

2.9

 

3.4

13.8

 

3.2

 

-0.2

 

 

65.3

20.4

2.9

 

2.1

14.0

 

3.1

 

-1.5

 

 

62.5

16.2

2.9

 

6.4

9.7

 

3.1

 

2.4

1600

 

64

18.2

3.0

 

5.0

10.8

 

3.2

 

1.0

 

 

65.3

19.6

3.0

 

3.1

12.2

 

3.2

 

-0.7

 

 

62.5

13.3

2.9

 

6.6

6.2

 

3.0

 

1.4

2000

 

64

14.8

2.9

 

4.7

7.2

 

3.0

 

-0.1

 

 

62

15.8

2.9

 

3.1

8.0

 

3.0

 

-1.5

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

72

Johnson Controls Unitary Products

Page 72
Image 72
York R-410A ZH/ZJ/ZR Series manual ZR049 4.0 Ton Reheat, Johnson Controls Unitary Products