York R-410A ZH/ZJ/ZR Series manual ZR037-150Side Duct Application, ZR037 3.0 Ton Side Duct

Models: R-410A ZH/ZJ/ZR Series

1 206
Download 206 pages 7.86 Kb
Page 116
Image 116
ZR037-150 Side Duct Application

528150-YTG-G-1210

ZR037-150 Side Duct Application

ZR037 (3.0 Ton) Side Duct

Air

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

Flow

 

0.2

 

0.4

 

0.6

 

0.8

 

1.0

1.2

 

1.4

 

1.6

 

1.8

 

2.0

 

(CFM)

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

FS4

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

Hi Static 1.5 HP & Drive

 

 

 

900

480

0.4

582

0.4

673

0.5

756

0.5

830

0.6

898

0.7

960

0.8

1018

0.9

1072

1.0

1124

1.1

1000

489

0.4

591

0.4

682

0.5

764

0.6

839

0.6

907

0.7

969

0.8

1026

0.9

1080

1.0

1132

1.1

1100

500

0.4

602

0.4

693

0.5

776

0.6

850

0.6

918

0.7

980

0.8

1038

0.9

1092

1.0

1144

1.1

1200

513

0.4

614

0.5

706

0.5

788

0.6

863

0.7

931

0.8

993

0.8

1050

0.9

1104

1.0

1156

1.1

1300

525

0.4

627

0.5

719

0.6

801

0.6

876

0.7

943

0.8

1005

0.9

1063

1.0

1117

1.1

1169

1.2

1400

537

0.5

639

0.5

731

0.6

813

0.7

888

0.7

955

0.8

1017

0.9

1075

1.0

1129

1.1

1181

1.2

1500

549

0.5

650

0.6

742

0.6

824

0.7

899

0.8

966

0.9

1028

0.9

1086

1.0

1140

1.1

1192

1.2

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

ZR049 (4.0 Ton) Side Duct

Air

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

 

 

 

Flow

0.2

 

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

2.0

(CFM

RPM

BHP

RPM BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

 

RPM

BHP

 

1.5 HP & Field

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

 

 

 

Hi Static 1.5 HP & Drive

 

 

 

 

 

 

Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1200

513

0.4

 

614

0.5

 

706

0.5

 

788

0.6

 

863

0.7

 

931

0.8

 

993

0.8

 

1050

0.9

 

1104

1.0

 

1156

1.1

 

 

 

 

 

 

 

 

 

1300

525

0.4

 

627

0.5

 

719

0.6

 

801

0.6

 

876

0.7

 

943

0.8

 

1005

0.9

 

1063

1.0

 

1117

1.1

 

1169

1.2

1400

537

0.5

 

639

0.5

 

731

0.6

 

813

0.7

 

888

0.7

 

955

0.8

 

1017

0.9

 

1075

1.0

 

1129

1.1

 

1181

1.2

1500

549

0.5

 

650

0.6

 

742

0.6

 

824

0.7

 

899

0.8

 

966

0.9

 

1028

0.9

 

1086

1.0

 

1140

1.1

 

1192

1.2

1600

558

0.6

 

660

0.6

 

752

0.7

 

834

0.8

 

909

0.8

 

976

0.9

 

1038

1.0

 

1096

1.1

 

1150

1.2

 

1202

1.3

1700

566

0.6

 

668

0.7

 

760

0.7

 

842

0.8

 

917

0.9

 

984

1.0

 

1046

1.1

 

1104

1.1

 

1158

1.2

 

1210

1.4

1800

573

0.7

 

675

0.7

 

766

0.8

 

849

0.9

 

923

1.0

 

991

1.0

 

1053

1.1

 

1110

1.2

 

1164

1.3

 

1216

1.4

1900

577

0.8

 

679

0.8

 

771

0.9

 

853

1.0

 

928

1.0

 

995

1.1

 

1057

1.2

 

1115

1.3

 

1169

1.4

 

1221

1.5

2000

580

0.8

 

682

0.9

 

773

1.0

 

856

1.0

 

930

1.1

 

998

1.2

 

1060

1.3

 

1117

1.4

 

1172

1.5

 

1224

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS4

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

ZR061 (5.0 Ton) Side Duct

Air

Available External Static Pressure - IWG1

Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

(CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

Hi Static 2 HP & Drive

 

 

 

 

 

1500

616

0.5

685

0.6

766

0.7

833

0.8

905

0.9

975

1.0

1035

1.0

1101

1.1

1163

1.2

1229

1.3

1600

638

0.6

707

0.7

781

0.7

848

0.8

920

0.9

990

1.0

1050

1.1

1104

1.1

1166

1.2

1232

1.3

1700

655

0.6

724

0.7

796

0.8

863

0.9

935

1.0

1005

1.1

1064

1.1

1109

1.2

1172

1.3

1238

1.4

1800

670

0.7

739

0.8

810

0.8

877

0.9

949

1.0

1018

1.1

1078

1.2

1117

1.2

1179

1.3

1245

1.5

1900

686

0.7

755

0.8

823

0.9

890

1.0

962

1.1

1032

1.2

1091

1.2

1125

1.3

1187

1.4

1253

1.5

2000

702

0.8

772

0.9

836

1.0

903

1.1

975

1.2

1045

1.3

1078

1.3

1135

1.4

1197

1.5

1263

1.6

2100

722

0.9

791

1.0

849

1.0

916

1.1

988

1.2

1058

1.3

1089

1.4

1147

1.5

1209

1.6

1275

1.7

2200

745

0.9

814

1.0

861

1.1

928

1.2

1000

1.3

1050

1.4

1102

1.5

1159

1.6

1221

1.7

1287

1.8

2300

772

1.0

841

1.1

874

1.2

941

1.3

1013

1.4

1064

1.5

1115

1.6

1173

1.7

1235

1.8

-

-

2400

804

1.1

832

1.2

886

1.3

953

1.4

1033

1.4

1078

1.6

1130

1.7

1188

1.8

-

-

-

-

2500

841

1.2

844

1.3

898

1.4

965

1.5

1049

1.5

1094

1.7

-

-

-

-

2 HP & Field Supplied Drive

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

116