ZJ078 (6.5 Ton) Side Duct

528150-YTG-G-1210

ZJ078 (6.5 Ton) Side Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

FS4

 

 

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

Hi Static 2 HP & Drive

 

1800

514

0.15

 

586

0.33

657

0.52

727

0.71

794

0.89

857

1.07

917

1.23

972

1.38

1021

1.50

1064

1.59

2000

529

0.23

 

601

0.41

672

0.60

741

0.79

808

0.97

872

1.15

931

1.31

986

1.46

1036

1.58

1079

1.67

2200

544

0.33

 

616

0.51

687

0.69

756

0.88

823

1.07

886

1.24

946

1.41

1001

1.55

1051

1.67

1094

1.77

2400

559

0.43

 

631

0.61

702

0.80

771

0.98

838

1.17

902

1.35

961

1.51

1016

1.65

1066

1.78

1109

1.87

2600

574

0.54

 

646

0.72

717

0.91

787

1.10

853

1.28

917

1.46

977

1.62

1032

1.77

1081

1.89

1124

1.98

2800

590

0.67

 

662

0.85

733

1.03

802

1.22

869

1.41

933

1.59

993

1.75

1047

1.89

1097

2.02

1140

2.11

3000

607

0.80

 

679

0.98

750

1.17

819

1.36

886

1.54

949

1.72

1009

1.88

1064

2.03

1113

2.15

1157

2.24

3200

624

0.95

 

695

1.13

766

1.31

836

1.50

903

1.69

966

1.86

1026

2.03

1081

2.17

1130

2.29

1173

2.39

3400

641

1.10

 

713

1.28

784

1.47

853

1.66

920

1.84

984

2.02

1043

2.18

1098

2.33

1148

2.45

1191

2.54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS4

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

ZJ090 (7.5 Ton) Side Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

 

FS4

 

 

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

Hi Static 3 HP & Drive

 

2000

-

-

 

656

0.24

711

0.48

768

0.73

826

0.96

886

1.19

945

1.41

1003

1.61

1058

1.79

1110

1.95

2200

619

0.07

 

670

0.32

724

0.57

781

0.81

840

1.04

899

1.27

959

1.49

1016

1.69

1072

1.87

1124

2.04

2400

631

0.16

 

682

0.41

736

0.66

793

0.90

852

1.14

911

1.36

970

1.58

1028

1.78

1084

1.97

1136

2.13

2600

642

0.27

 

692

0.52

747

0.76

804

1.01

862

1.24

922

1.47

981

1.69

1039

1.89

1094

2.07

1146

2.24

2800

652

0.39

 

703

0.64

757

0.88

814

1.13

873

1.36

932

1.59

992

1.81

1049

2.01

1105

2.19

1157

2.36

3000

663

0.53

 

714

0.77

768

1.02

825

1.26

884

1.50

943

1.73

1003

1.94

1060

2.14

1116

2.33

1168

2.49

3200

675

0.68

 

726

0.92

780

1.17

837

1.41

896

1.65

955

1.88

1014

2.09

1072

2.29

1128

2.48

1180

2.64

3400

688

0.84

 

739

1.09

793

1.34

850

1.58

909

1.82

968

2.04

1027

2.26

1085

2.46

1141

2.65

1193

2.81

3600

703

1.03

 

753

1.28

807

1.52

864

1.76

923

2.00

983

2.23

1042

2.44

1100

2.64

1155

2.83

-

-

3800

718

1.23

 

769

1.47

823

1.72

880

1.96

939

2.20

998

2.43

1058

2.64

1115

2.84

1171

3.03

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

4.Field Supplied Drive.

ZJ102 (8.5 Ton) Side Duct

Available External Static Pressure - IWG1

Air Flow 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 (CFM)

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

 

Field Supplied Drive

 

 

Standard 2 HP & Drive

 

 

 

 

Hi Static 3 HP & Drive

 

 

2200

654

0.32

706

0.53

755

0.73

803

0.92

849

1.10

893

1.27

937

1.44

979

1.62

1020

1.79

1061

1.96

2400

664

0.43

716

0.64

765

0.83

813

1.02

859

1.20

904

1.38

947

1.55

989

1.72

1030

1.89

1071

2.07

2600

675

0.53

726

0.74

776

0.94

824

1.12

870

1.30

914

1.48

957

1.65

1000

1.82

1041

1.99

1082

2.17

2800

686

0.63

738

0.84

787

1.04

835

1.23

881

1.41

925

1.58

969

1.76

1011

1.93

1052

2.10

1093

2.27

3000

699

0.75

750

0.96

800

1.16

847

1.34

893

1.52

938

1.70

981

1.87

1024

2.04

1065

2.21

1106

2.39

3200

713

0.88

764

1.09

814

1.28

861

1.47

907

1.65

952

1.83

995

2.00

1037

2.17

1079

2.34

1119

2.52

3400

728

1.02

779

1.23

829

1.43

877

1.61

923

1.79

967

1.97

1010

2.14

1053

2.31

1094

2.48

1135

2.66

3600

745

1.18

796

1.39

846

1.59

893

1.77

939

1.95

984

2.13

1027

2.30

1069

2.47

1111

2.64

1152

2.82

3800

763

1.36

815

1.57

864

1.76

912

1.95

958

2.13

1002

2.31

1046

2.48

1088

2.65

1129

2.82

1170

3.00

4000

783

1.55

835

1.76

884

1.96

932

2.15

978

2.33

1022

2.50

1066

2.67

1108

2.84

1149

3.02

1190

3.19

4200

805

1.77

856

1.98

906

2.17

953

2.36

999

2.54

1044

2.72

1087

2.89

1129

3.06

1171

3.23

1211

3.41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP & Field Supplied Drive

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.932.

Johnson Controls Unitary Products

111

Page 111
Image 111
York R-410A ZH/ZJ/ZR Series manual YTG-G-1210, ZJ078 6.5 Ton Side Duct, ZJ090 7.5 Ton Side Duct, ZJ102 8.5 Ton Side Duct