ZJ061 (5.0 Ton) (Continued)

528150-YTG-G-1210

ZJ061 (5.0 Ton) (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

58.5

4.9

22.3

20.4

14.9

-

-

-

53.4

5.3

21.9

17.7

13.3

-

-

-

1250

 

72

52.4

4.8

33.7

28.3

22.8

17.4

-

-

47.6

5.2

31.8

26.4

21.0

15.6

-

-

 

67

46.3

4.7

45.1

36.1

30.7

25.2

19.8

-

41.7

5.1

41.7

34.1

28.7

23.4

18.0

-

 

 

 

 

62

43.3

4.7

43.3

43.3

34.8

29.3

23.9

18.4

40.0

5.0

40.0

40.0

31.2

25.8

20.5

15.1

 

 

77

60.5

4.9

29.6

23.1

16.7

-

-

-

55.1

5.3

29.6

21.3

14.9

-

-

-

 

 

72

54.2

4.9

38.3

31.9

25.5

19.0

-

-

49.1

5.3

36.3

29.9

23.6

17.2

-

-

1500

 

67

47.9

4.8

47.1

40.7

34.3

27.8

21.4

-

43.0

5.2

43.0

38.6

32.2

25.8

19.5

-

 

 

62

44.8

4.7

44.8

44.8

38.9

32.4

26.0

19.6

41.2

5.1

41.2

41.2

35.0

28.6

22.3

15.9

 

 

57

43.1

4.7

43.1

43.1

38.5

32.1

25.7

19.2

39.7

5.1

39.7

39.7

35.4

29.0

22.6

16.3

 

 

77

62.5

5.0

36.8

25.9

18.4

-

-

-

56.8

5.4

37.4

24.8

16.5

-

-

-

 

 

72

56.0

4.9

43.0

35.6

28.1

20.7

-

-

50.6

5.3

40.8

33.5

26.1

18.7

-

-

1750

 

67

49.5

4.8

49.1

45.3

37.8

30.4

23.0

-

44.3

5.2

44.3

43.0

35.7

28.3

20.9

-

 

 

62

46.3

4.7

46.3

46.3

42.9

35.5

28.1

20.7

42.5

5.1

42.5

42.5

38.8

31.4

24.1

16.7

 

 

57

44.5

4.7

44.5

44.5

42.6

35.1

27.7

20.3

40.9

5.1

40.9

40.9

39.2

31.8

24.5

17.1

 

 

77

64.5

5.0

44.1

28.6

20.2

-

-

-

58.5

5.5

45.1

28.4

18.1

-

-

-

 

 

72

57.8

5.0

47.6

39.2

30.8

22.4

-

-

52.1

5.4

45.4

37.0

28.6

20.3

-

-

2000

 

67

51.1

4.9

51.1

49.8

41.4

33.0

24.6

-

45.6

5.3

45.6

45.6

39.2

30.8

22.4

-

 

 

62

47.8

4.8

47.8

47.8

47.0

38.6

30.2

21.8

43.8

5.2

43.8

43.8

42.6

34.2

25.9

17.5

 

 

57

45.9

4.8

45.9

45.9

46.6

38.2

29.8

21.4

42.2

5.2

42.2

42.2

42.2

34.7

26.3

17.9

 

 

72

58.7

5.0

51.8

42.5

33.3

24.0

-

-

52.7

5.4

49.5

40.2

31.0

21.8

-

-

2250

 

67

51.9

4.9

51.9

51.3

44.7

35.5

26.2

-

46.2

5.3

46.2

46.2

42.4

33.1

23.9

-

 

62

48.6

4.8

48.6

48.6

48.2

38.9

29.6

20.4

44.3

5.2

44.3

44.3

43.7

34.5

25.3

16.1

 

 

 

 

57

46.7

4.8

46.7

46.7

47.0

37.7

28.5

19.2

42.7

5.2

42.7

42.7

42.7

33.9

24.7

15.5

 

 

72

59.6

5.0

55.9

45.8

35.7

25.6

-

-

53.4

5.4

53.4

43.4

33.4

23.3

-

-

2500

 

67

52.7

4.9

52.7

52.7

48.0

37.9

27.7

-

46.8

5.3

46.8

46.8

45.6

35.5

25.4

-

 

62

49.3

4.8

49.3

49.3

49.3

39.2

29.1

19.0

44.9

5.2

44.9

44.9

44.9

34.8

24.7

14.6

 

 

 

 

57

47.4

4.8

47.4

47.4

47.4

37.3

27.1

17.0

43.3

5.2

43.3

43.3

43.3

33.2

23.1

13.0

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.