Indoor Sound Power Levels (Horizontal Ducted Inlet, High Static Belt Drive)

UNIT DESCRIPTION / MODEL

 

 

 

ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

 

 

Horizontal (Side Return) Ducted Inlet

 

 

 

Indoor Blower Speed (RPM)

876 - 4 Turns Open Equivalent

 

1,064 - 1/2 Turn Open Equivalent

 

1,190 - 2.5 Turns Open Equivalent1

External Static Pressure (IWG)

 

1.0

 

 

 

1.6

 

 

2.0 1

Nominal Airflow (CFM)

 

1,200

 

 

 

1,100

 

 

1,000

 

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

0.64

 

 

 

0.93

 

 

1.08

 

 

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

 

 

ID Blower

 

Cooling

 

ID Blower

 

Cooling

Only (dB)

 

Operation2

(dB)

 

Only (dB)

 

Operation2 (dB)

 

Only (dB)

 

Operation2 (dB)

 

 

 

 

 

 

63

75

 

80

 

 

81

 

81

 

81

 

83

 

 

 

 

 

 

 

 

 

 

 

 

 

125

69

 

71

 

 

71

 

73

 

73

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

250

62

 

68

 

 

66

 

71

 

68

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

500

54

 

56

 

 

57

 

59

 

59

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

52

 

56

 

 

56

 

58

 

58

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

47

 

49

 

 

52

 

52

 

54

 

56

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

43

 

45

 

 

48

 

49

 

51

 

53

 

 

 

 

 

 

 

 

 

 

 

 

 

8000

43

 

45

 

 

45

 

46

 

47

 

48

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Requires driven pulley #AK-56, normal high static pulley is an #AK-69.

2.Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR049 / 4 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

 

Horizontal (Side Return) Ducted Inlet

 

 

 

 

 

 

 

 

 

Indoor Blower Speed (RPM)

965 - 5.5 Turns Open Equivalent

 

1,088 - 4 Turns Open Equivalent

 

1,186 - 2.5 Turns Open Equivalent

 

 

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

1.0

 

 

1.6

 

 

2.0

 

 

 

 

 

 

 

 

 

Nominal Airflow (CFM)

 

1,600

 

 

1,400

 

 

1,200

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

0.86

 

 

1.03

 

 

1.13

 

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

 

ID Blower

 

Cooling

 

ID Blower

 

Cooling

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

 

 

 

 

 

63

74

 

80

 

77

 

80

 

81

 

81

 

 

 

 

 

 

 

 

 

 

 

 

125

69

 

74

 

72

 

75

 

75

 

76

 

 

 

 

 

 

 

 

 

 

 

 

250

68

 

68

 

68

 

69

 

70

 

71

 

 

 

 

 

 

 

 

 

 

 

 

500

62

 

62

 

60

 

61

 

61

 

63

 

 

 

 

 

 

 

 

 

 

 

 

1000

60

 

61

 

58

 

58

 

59

 

60

 

 

 

 

 

 

 

 

 

 

 

 

2000

57

 

57

 

53

 

54

 

55

 

56

 

 

 

 

 

 

 

 

 

 

 

 

4000

56

 

56

 

49

 

50

 

51

 

52

 

 

 

 

 

 

 

 

 

 

 

 

8000

54

 

54

 

45

 

47

 

47

 

48

 

 

 

 

 

 

 

 

 

 

 

 

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

128

Johnson Controls Unitary Products

Page 128