Manual background

528150-YTG-G-1210

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR061 / 5 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

 

Vertical (Bottom Return) Ducted Inlet

 

 

 

 

 

 

 

 

 

Indoor Blower Speed (RPM)

1,039 - 5 Turns Open Equivalent

 

1,143 - 3 Turns Open Equivalent

 

1,201 - 2 Turns Open Equivalent

 

 

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

1.0

 

 

1.6

 

 

2.0

 

 

 

 

 

 

 

 

 

Nominal Airflow (CFM)

 

2,000

 

 

1,800

 

 

1,600

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

1.11

 

 

1.25

 

 

1.39

 

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

 

ID Blower

 

Cooling

 

ID Blower

 

Cooling

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

Only (dB)

 

Operation1 (dB)

 

 

 

 

 

 

63

79

 

80

 

77

 

77

 

81

 

81

 

 

 

 

 

 

 

 

 

 

 

 

125

74

 

75

 

71

 

73

 

73

 

74

 

 

 

 

 

 

 

 

 

 

 

 

250

63

 

65

 

63

 

64

 

63

 

65

 

 

 

 

 

 

 

 

 

 

 

 

500

62

 

63

 

64

 

64

 

62

 

62

 

 

 

 

 

 

 

 

 

 

 

 

1000

61

 

61

 

61

 

61

 

59

 

59

 

 

 

 

 

 

 

 

 

 

 

 

2000

55

 

56

 

55

 

56

 

54

 

55

 

 

 

 

 

 

 

 

 

 

 

 

4000

52

 

52

 

50

 

51

 

50

 

50

 

 

 

 

 

 

 

 

 

 

 

 

8000

47

 

47

 

46

 

46

 

46

 

46

 

 

 

 

 

 

 

 

 

 

 

 

1. Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Indoor Sound Power Levels (Vertical Ducted Discharge, High Static Belt Drive)

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR037 / 3 Ton / High Static Belt Drive

 

 

TEST CONFIGURATION

 

 

Vertical (Bottom Supply) Ducted Discharge

 

 

Indoor Blower Speed (RPM)

920 - 3.0 Turns Open Equivalent

1,074 - Fully Closed Equivalent

1,189 - 2.0 Turns Open Equivalent1

External Static Pressure (IWG)

 

1.0

 

1.6

 

2.01

Nominal Airflow (CFM)

 

1,200

 

1,100

 

1,000

 

 

 

 

 

 

 

Blower Motor BHP

 

0.68

 

0.93

 

1.09

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower

 

Cooling

ID Blower

 

Cooling

ID Blower

 

Cooling

Only (dB)

 

Operation2 (dB)

Only (dB)

 

Operation2 (dB)

Only (dB)

 

Operation2 (dB)

 

 

 

 

63

81

 

82

81

 

81

82

 

82

 

 

 

 

 

 

 

 

 

 

125

78

 

78

78

 

78

81

 

81

 

 

 

 

 

 

 

 

 

 

250

69

 

70

70

 

71

74

 

74

 

 

 

 

 

 

 

 

 

 

500

67

 

68

68

 

69

71

 

71

 

 

 

 

 

 

 

 

 

 

1000

62

 

63

67

 

68

70

 

71

 

 

 

 

 

 

 

 

 

 

2000

60

 

61

62

 

63

65

 

66

 

 

 

 

 

 

 

 

 

 

4000

61

 

61

63

 

63

66

 

66

 

 

 

 

 

 

 

 

 

 

8000

54

 

55

57

 

57

60

 

61

 

 

 

 

 

 

 

 

 

 

1.Requires driven pulley #AK-56, normal high static pulley is an #AK-69.

2.Differentials for Cooling Operation (IDB, COMP, & ODF) are logarithmically calculated from the horizontal flow sound test.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

132

Johnson Controls Unitary Products

Page 132
Image 132
York R-410A ZH/ZJ/ZR Series manual Indoor Blower Speed RPM