ZH150 (12.5 Ton) (Continued)

528150-YTG-G-1210

ZH150 (12.5 Ton) (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

158.4

14.6

65.6

53.5

40.6

-

-

-

147.6

16.1

60.0

50.8

38.1

-

-

-

3125

 

72

144.6

14.5

88.2

75.4

62.5

49.6

-

-

134.2

16.0

84.9

72.2

59.5

46.8

-

-

 

67

130.9

14.3

110.9

97.3

84.4

71.5

58.7

-

120.9

15.8

107.4

93.6

80.9

68.2

55.5

-

 

 

 

 

62

120.5

14.0

120.5

120.5

104.7

91.9

79.0

66.1

112.3

15.6

112.3

112.3

100.7

87.9

75.2

62.5

 

 

77

162.2

14.7

73.1

58.6

44.1

-

-

-

150.8

16.1

69.9

55.6

41.3

-

-

-

 

 

72

148.1

14.5

96.9

82.4

67.9

53.3

-

-

137.2

16.0

93.0

78.7

64.5

50.2

-

-

3750

 

67

134.0

14.3

120.6

106.1

91.6

77.1

62.6

-

123.5

15.8

116.2

101.9

87.6

73.4

59.1

-

 

 

62

123.3

14.1

123.3

123.3

113.7

99.2

84.7

70.2

114.8

15.6

114.8

114.8

109.0

94.7

80.5

66.2

 

 

57

121.8

14.1

121.8

121.8

110.3

95.8

81.2

66.7

112.1

15.6

112.1

112.1

102.2

88.0

73.7

59.4

 

 

77

165.9

14.7

80.6

63.7

47.6

-

-

-

154.1

16.1

79.7

60.3

44.5

-

-

-

 

 

72

151.5

14.5

105.5

89.4

73.2

57.1

-

-

140.1

15.9

101.1

85.3

69.5

53.6

-

-

4375

 

67

137.1

14.3

130.4

115.0

98.9

82.7

66.6

-

126.2

15.8

125.0

110.2

94.4

78.6

62.7

-

 

 

62

126.2

14.1

126.2

126.2

122.7

106.5

90.4

74.2

117.2

15.5

117.2

117.2

117.2

101.6

85.7

69.9

 

 

57

124.6

14.1

124.6

124.6

119.0

102.8

86.7

70.5

114.6

15.6

114.6

114.6

110.1

94.3

78.4

62.6

 

 

77

169.7

14.7

88.1

68.8

51.0

-

-

-

157.3

16.1

89.6

65.1

47.7

-

-

-

 

 

72

155.0

14.5

114.2

96.4

78.6

60.8

-

-

143.1

15.9

109.2

91.8

74.4

57.0

-

-

5000

 

67

140.2

14.3

140.2

123.9

106.1

88.3

70.5

-

128.9

15.7

128.9

118.6

101.1

83.7

66.3

-

 

 

62

129.1

14.1

129.1

129.1

131.7

113.9

96.1

78.3

119.7

15.5

119.7

119.7

119.7

108.4

91.0

73.6

 

 

57

127.4

14.2

127.4

127.4

127.7

109.9

92.1

74.3

117.0

15.6

117.0

117.0

117.0

100.6

83.2

65.7

 

 

72

155.6

14.6

123.2

103.8

84.3

64.9

-

-

143.2

16.0

118.9

99.7

80.4

61.2

-

-

5625

 

67

140.8

14.4

140.8

132.6

113.9

94.4

74.9

-

128.9

15.8

128.9

127.5

109.3

90.0

70.8

-

 

62

129.6

14.1

129.6

129.6

130.9

111.4

92.0

72.5

119.8

15.6

119.8

119.8

119.8

103.6

84.3

65.1

 

 

 

 

57

127.9

14.2

127.9

127.9

128.1

108.6

89.1

69.7

117.0

15.6

117.0

117.0

117.0

98.3

79.0

59.8

 

 

72

156.2

14.6

132.3

111.2

90.1

69.0

-

-

143.3

16.0

128.6

107.5

86.4

65.3

-

-

6250

 

67

141.4

14.4

141.4

141.4

121.6

100.5

79.4

-

129.0

15.8

129.0

129.0

117.4

96.3

75.2

-

 

62

130.1

14.2

130.1

130.1

130.1

109.0

87.9

66.8

119.9

15.6

119.9

119.9

119.9

98.8

77.7

56.5

 

 

 

 

57

128.4

14.2

128.4

128.4

128.4

107.3

86.2

65.1

117.1

15.7

117.1

117.1

117.1

96.0

74.9

53.8

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.