528150-YTG-G-1210

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT DESCRIPTION / MODEL

 

 

ZH/ZJ/ZR061 / 5 Ton / Standard Static Belt Drive

 

 

 

 

TEST CONFIGURATION

 

 

Horizontal (Side Return) Ducted Inlet

 

 

 

 

Indoor Blower Speed (RPM)

814 - 3 Turns Open Equivalent

918 - 1 Turn Open Equivalent

 

 

 

 

 

 

 

 

 

External Static Pressure (IWG)

 

0.6

 

0.8

 

 

 

 

 

 

 

 

 

Airflow (CFM)

 

1700

 

1950

 

 

 

 

 

 

 

 

 

Blower Motor BHP

 

0.42

 

0.88

 

 

 

 

 

 

 

 

 

 

 

Octave Center Freq. Hz

ID Blower Only (dB)

 

Cooling Operation1 (dB)

ID Blower Only (dB)

 

Cooling Operation1 (dB)

 

63

77

 

81

85

 

82

 

 

 

 

 

 

 

 

 

 

125

71

 

80

68

 

81

 

 

 

 

 

 

 

 

 

 

250

63

 

67

64

 

68

 

 

 

 

 

 

 

 

 

 

500

58

 

60

60

 

61

 

 

 

 

 

 

 

 

 

 

1000

56

 

57

58

 

59

 

 

 

 

 

 

 

 

 

 

2000

52

 

53

55

 

55

 

 

 

 

 

 

 

 

 

 

4000

51

 

51

54

 

54

 

 

 

 

 

 

 

 

 

 

8000

47

 

47

48

 

48

 

 

 

 

 

 

 

 

 

 

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.

Indoor Sound Power Levels (Horizontal Ducted Discharge, Standard Static Belt Drive)

UNIT DESCRIPTION / MODEL

 

ZH/ZJ/ZR037 / 3 Ton / Standard Static Belt Drive

 

TEST CONFIGURATION

 

Horizontal (Side Supply) Ducted Discharge

 

Indoor Blower Speed (RPM)

610 - 3 Turns Open Equivalent

710 - 1 Turn Open Equivalent

External Static Pressure (IWG)

 

0.5

 

0.6

Airflow (CFM)

 

850

 

950

Blower Motor BHP

 

0.37

 

0.42

Octave Center Freq. Hz

ID Blower Only (dB)

Cooling Operation1 (dB)

ID Blower Only (dB)

Cooling Operation1 (dB)

63

77

78

79

79

125

74

75

75

76

250

66

68

70

70

500

61

61

65

64

1000

60

62

65

66

2000

52

52

58

58

4000

52

52

59

60

8000

44

44

50

50

1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.

Tested in accordance with ARI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment.

Testing datum includes effect of standard inlet air filters.

Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.

Test duct termination is flush with reverberant room wall.

Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.