ZR061 (5.0 Ton) Reheat

 

 

 

 

 

 

 

 

 

 

 

 

528150-YTG-G-1210

 

 

 

 

 

 

 

 

 

 

 

 

ZR061 (5.0 Ton) Reheat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air on

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

Evaporator Coil

 

Total

Total

 

Sensible Capacity (MBh)

Total

 

Total

 

Sensible Capacity (MBh)

 

 

(- indicates heating)

 

 

(- indicates heating)

 

 

 

 

 

 

 

 

 

 

 

Capacity1

Input

 

 

Capacity1

 

Input

 

 

CFM

 

WB

 

(MBh)

(kW)2

 

Return Dry Bulb (°F)

(MBh)

 

(kW)2

 

Return Dry Bulb (°F)

 

(°F)

 

 

75

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40 °F

 

 

 

 

50 °F

 

 

62.5

 

26.8

3.1

 

8.4

29.3

 

3.2

 

10.7

1750

 

64

 

28.9

3.1

 

6.4

32.4

 

3.2

 

9.2

 

 

65.3

 

30.0

3.1

 

4.8

34.7

 

3.2

 

7.3

 

 

62.5

 

29.2

3.1

 

11.0

30.3

 

3.2

 

11.9

2000

 

64

 

30.8

3.1

 

8.6

32.3

 

3.2

 

9.9

 

 

65.3

 

31.4

3.1

 

5.8

35.3

 

3.2

 

8.4

 

 

62.5

 

29.8

3.1

 

10.5

29.6

 

3.2

 

11.1

2250

 

64

 

31.2

3.1

 

7.6

32.1

 

3.2

 

8.5

 

 

65.3

 

31.4

3.1

 

6.0

34.5

 

3.2

 

6.2

 

 

 

 

 

 

60 °F

 

 

 

 

70 °F

 

 

62.5

 

26.7

3.3

 

9.2

24.5

 

3.4

 

8.0

1750

 

64

 

28.9

3.3

 

6.9

27.0

 

3.4

 

6.4

 

 

65.3

 

31.6

3.3

 

5.4

28.7

 

3.4

 

4.3

 

 

62.5

 

27.9

3.3

 

10.9

25.0

 

3.4

 

9.0

2000

 

64

 

31.0

3.3

 

8.4

27.3

 

3.4

 

6.9

 

 

65.3

 

32.9

3.3

 

6.7

29.6

 

3.4

 

4.9

 

 

62.5

 

26.8

3.3

 

9.5

23.6

 

3.4

 

7.3

2250

 

64

 

29.5

3.3

 

6.9

26.1

 

3.4

 

4.7

 

 

62

 

31.7

3.3

 

4.5

28.2

 

3.4

 

2.7

 

 

 

 

 

 

75 °F

 

 

 

 

80 °F

 

 

62.5

 

22.8

3.5

 

7.1

21.3

 

3.5

 

6.3

1750

 

64

 

25.5

3.5

 

5.1

23.9

 

3.5

 

4.6

 

 

65.3

 

27.8

3.5

 

3.3

25.8

 

3.5

 

2.7

 

 

62.5

 

23.2

3.5

 

8.0

21.3

 

3.5

 

7.3

2000

 

64

 

25.7

3.5

 

5.9

23.7

 

3.5

 

5.3

 

 

65.3

 

27.8

3.5

 

4.3

25.7

 

3.5

 

3.6

 

 

62.5

 

21.6

3.4

 

6.8

19.5

 

3.5

 

5.6

2250

 

64

 

23.8

3.5

 

4.5

22.0

 

3.5

 

3.1

 

 

65.3

 

26.1

3.5

 

1.9

24.1

 

3.5

 

1.0

 

 

 

 

 

 

85 °F

 

 

 

 

95 °F

 

 

62.5

 

17.4

3.5

 

3.9

8.3

 

3.8

 

-1.8

1750

 

64

 

19.7

3.6

 

2.0

9.8

 

3.8

 

-3.9

 

 

65.3

 

21.6

3.6

 

-0.3

11.2

 

3.9

 

-5.3

 

 

62.5

 

17.3

3.6

 

5.0

7.1

 

3.8

 

-0.9

2000

 

64

 

19.4

3.6

 

2.5

8.8

 

3.8

 

-3.0

 

 

65.3

 

20.9

3.6

 

0.5

10.3

 

3.9

 

-5.2

 

 

62.5

 

16.0

3.5

 

3.5

5.0

 

3.8

 

-3.3

2250

 

64

 

18.0

3.6

 

0.4

6.1

 

3.8

 

-6.2

 

 

62

 

19.4

3.6

 

-1.7

8.3

 

3.9

 

-8.0

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

75

Page 75
Image 75
York R-410A ZH/ZJ/ZR Series manual ZR061 5.0 Ton Reheat, Johnson Controls Unitary Products