Generator Location

The actual physical location of your generator has a direct affect on:

1.The amount of plumbing required to fuel your generator.

2.The amount of wiring required to control and connect your generator.

Specific location guidelines are discussed in the installation manual. Acquaint yourself with that information and confer with your installer. Be sure to ask how your site might affect installation costs and compliance with local codes and standards.



WARNING Running engine gives off carbon monoxide, an odorless, colorless, poison gas.

Breathing carbon monoxide could result in death,

serious injury, headache, fatigue, dizziness, vomiting, confusion, seizures, nausea or fainting.

t Operate this product ONLY outdoors in an area that will not accumulate deadly exhaust gas.

t Keep exhaust gas away from any windows, doors, ventilation intakes, soffit vents, crawl spaces, open garage doors or other openings that can allow exhaust gas

to enter inside or be drawn into a potentially occupied building or structure.

t Carbon monoxide detector(s) MUST be installed and maintained indoors according to the manufacturer’s instructions/recommendations. Smoke alarms cannot detect carbon monoxide gas.

t %0/05JOTUBMMHFOFSBUPSXIFSFFYIBVTUHBTDPVME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

accumulate and enter inside or be drawn into a



 

t &OTVSFFYIBVTUHBTJTLFQUBXBZGSPNBOZXJOEPXT

potentially occupied building or structure.

 

t #Z MBXJUJTSFRVJSFEJONBOZTUBUFTUPIBWFB$BSCPO

 

 

 

 

 

doors, ventilation intakes, soffit vents, crawl spaces,

 

 

 

 

 

open garage doors or other openings that can

Monoxide (CO) detector in operating condition in

 

 

 

 

 

 

 

 

 

 

allow exhaust gas to enter inside or be drawn into

your home. Carbon monoxide detector(s) (A) MUST

 

 

 

 

 

 

 

 

 

 

a potentially occupied

building or structure. Your

be installed and maintained indoors according to the

 

 

 

 

 

 

 

 

 

 

neighbor’s home ma

 

 

 

 

osed to the engine exhaust

manufacturer’s instructions/recommendations. A CO

 

 

 

 

 

y be exp

 

 

 

 

 

from your standb

 

 

 

 

 

 

 

and must be considered

monitor is an electronic device that detects hazardous

 

 

 

 

 

y generator

 

 

 

 

 

when installing

 

 

 

 

 

 

generator.

levels of CO. When there is a buildup of CO, the

 

 

 

 

 

your stand

 

 

 

t 8JOEBOEB

JS



 

 

 

 

 

TIPVMECFUBLFOJOUP

monitor will alert the occupants by flashing visual

 

 

 

DVSSFOUT

 

 

 

 

 

indicator light and alarm. Smoke alarms cannot detect

 

 

 

 

 

consid

ration when

positioning generator.

CO gas.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See the

nstallation manual for full details on safe generator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

location.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exhaust heat/gases could ignite

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

combustibles or structures resulting in death,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

serious injury and/or property damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOT

 

 

 

 

 

 

 

 

OU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t Exhaust outlet side of weatherproof enclosure must

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

have at least 5 ft. (1.5 m) minimum clearance from any

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F

 

 

 

 

 

 

 

 

 

 

structure, shrubs, trees, or any kind of vegetation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t Standby generator weatherproof enclosure must be at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

least 5 ft. (1.5 m) from windows, doors, any wall opening,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shrubs or vegetation over 12 in. (30.5 cm) in height.

 

 

 

 

 

 

 

 

 

 

 

REPR

 

 

 

 

 

CTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t Standby generator weatherproof enclosure must have a

minimum of 5 ft. (1.5 m) overhead clearance from any structure, overhang or trees.

t DO NOT place weatherproof enclosure under a deck or other type of structure that may confine airflow.

t USE ONLY flexible steel fuel line provided. Connect provided fuel line to generator. DO NOT use with or substitute any other flexible fuel line.

t Smoke detector(s) MUST be installed and maintained indoors according to the manufacturer’s instructions/ recommendations. Carbon monoxide alarms cannot detect smoke.

t DO NOT place weatherproof enclosure in manner other than shown in illustrations.

9

Image 9
Contents Generator Systems Where to Find Us Not Reproduction ForSave these original instructions for future reference Reproduction Safety Symbols and Meanings Important Safety InstructionsNot ReprVictim ReproRoduction GeneralLocation Guidelines to insure for For the Installing Dealer/Contractor InstallationFor the Home Owner OrientatFlammable and explosive, which could Fuel FactorsCause burns, fire or explosion resulting Death, serious injury and/or propertyGenerator Location Repr CtionNot For ReproductionDelivery Inspection Generator is supplied with Not includedControls RODGenerator Lifting Holes Provided at each corner for lifting generatorSystem Control Panel Auto modeSET Exercise Used to set Detection SystemTo open access door Access PortsTo close access door To remove roof and dividerTo install side panels REPTo remove exhaust panel Operation ReproduExercise timer. See Setting Exercise Timer MaintenanceFault Detection System Fault CodesUction Transfer Switch Fault FC8 High Temperature FC7Tion Engine MaintenanceChecking/Adding Engine Oil Changing Engine OilChanging Oil Filter Instruction will void Generator warranty GineAdd oil as described in Checking/Adding Engine Oil Ulting froService Spark Plugs Service Air CleanerMaintenance section REP OductionFuel System Inspection and Maintenance Clean Air Cooling SystemPressure Regulator Maintenance and Inspection Natural Gas/Propane Fuel SystemTest System Operation Simulate a Power Outage Servicing the Battery BatteryCharging the Battery ReprductionStorage When Calling for AssistanceProblem Cause Correction TroubleshootingProtech Standby Generators Reprodu CtionEngine Specifications Generator SpecificationsCommon Service Parts ReprodutionSistema generador Doméstico Not Reproduction For Controles UtilizaciónMantenimiento Símbolos sobre la seguridad y significados Conserve estas instruccionesSte Contacto directo con la víctimaCasas Advertencia El arranInstalación ReprodResponsabilidades del distribuidor/técnico instalador Orientación para el propietarioFactores relacionados con el combustible EraturasFORelevadas o enFactores cuando determinen la carga total del generador Ubicación del generador El generador doméstico incluye lo siguiente No incluye Inspección al momento de la entregaGenerador doméstico ControlesOrificios para horquilla elevadora Proporcionado en Cada esquina para levantar el generadorPara Panel de control del sistemaPara desmontar los paneles laterales PR UctionPara solta Que el techo abra ligeramente Levante el techo del generadorPara desmontar el panel de escape Prod ForPara instalar los paneles laterales  Permita que el equipo se enfríe antes de tocarloFuncionamiento automático UtilizaciónAceite de motor BateríaMantenimiento Paro del sistemaLas Restablecimiento del sistema de detección de fallas La sección Configuración del temporizador de prácticaEl motor no arranca FC4 Baja presión de aceite FC2Mantenimiento del generador Mantenimiento del motor Comprobación/adición de aceite para motorAceite del motor Cambio de aceite del motor Revisión del filtro de aireCambio del filtro de ceite Comprobación de holgura de las válvulas Revisión de las bujíasAjuste de En la sección MantenimientoDuction Circuito de combustible de gas natural/propanoDel temporizador de ejercicio Alimentación eléctrica Servicio la batería Cargar la bateríaAlmacenamiento Si llama a la fábricaDUC Tion Resolución de problemasPeríodos DE LA Garantía Generadores de reserva domésticos ProtechReprouction Especificaciones del generadorPartes de Servicio Comu Groupe électrogène Not Reproduction For Commandes InstallationFonctionnement ’Huile moteurRepr Uction Symboles de sécurité et Leur signDirect avec la victime Les Directives générales concernant l’emplacement afin ’installation Au détaillant ou à l’entrepreneur procédantConseils au propriétaire Le débit de gaz naturel dépend du combustible spécifique Facteurs relatifs au combustibleMais la dépréciation typique se situe entre 10 et 20% du Débit du gaz de pétrole liquéfiéRs de Emplacement de la génératriceArticles non fournis Vérification de la livraisonGroupe électrogène CommandesTableau de commande de système Portes d’accès Pour ouvrir une porte d’accèsPour fermer une porte d’accès Pour installer les panneaux latéraux ODU CTPour retirer le panneau d’échappement Fonctionnement Pour exécuter la procédure de réglage du cycle d’exercice Réglage de la minuterie du cycle d’exerciceArrêt du système EntreitenEmballement du moteur FC6 Basse tension génératrice, FC3Défaillance du commutateur de transfert FC8 Entretien du générateur Vérification/ajout d’huile à moteur Entretien du filtre à air Changement d’huile à moteurChangement du filtre à huile Le par un nouveauSolidement Installez la bougie d’allumage et serrez-laInspection et entretien du circuit d’alimentation Système au gaz naturel/propaneSource d’alimentation de service, la minuterie de Mettez l’alimentation électrique de serviceÉléments suivants Cylindre du collecteur d’échappement et que tous lesEntretien de la batterie Voir Batterie dans la section Considérations pourRechargez la batterie Remisage Communications avec le FabricantDépannage Étendue DE LA Garantie Génératrices résidentielles de secours ProtechReprodction Caractéristiques du produitPièces d’entretien courant

Generator Systems, GEN12AD-V specifications

The Ruud GEN12AD-V is a cutting-edge generator system designed to provide reliable and efficient power solutions for various applications, from residential to commercial use. With a robust design and advanced technology, the GEN12AD-V stands out in the market for its exceptional performance and functionality.

One of the main features of the Ruud GEN12AD-V is its powerful engine. Equipped with a high-performance, air-cooled, four-stroke engine, the generator ensures a steady output of 12,000 watts, making it suitable for running multiple appliances simultaneously, including air conditioning units, refrigerators, and power tools. The engine is designed for fuel efficiency, allowing longer operation times between refueling, which is a significant advantage during extended power outages.

Another notable aspect of the GEN12AD-V is its advanced inverter technology. This allows the generator to produce clean and stable power, minimizing harmonic distortion, which is crucial for sensitive electronics. The pure sine wave output ensures that devices such as laptops, gaming consoles, and medical equipment operate safely and efficiently.

The generator is also equipped with an intelligent monitoring system that provides real-time data on fuel levels, load capacity, and operational hours. This technology helps users manage their energy consumption effectively, ensuring that the generator is always operating within optimal parameters. Additionally, the unit features a user-friendly digital display that provides easy access to all vital information at a glance.

Durability is a hallmark of the Ruud GEN12AD-V, as it is built with a rugged steel frame designed to withstand harsh environmental conditions. The generator's housing is weather-resistant, ensuring protection from rain and debris, making it ideal for outdoor use. The system also incorporates advanced cooling mechanisms to prevent overheating, thereby extending its lifespan.

Safety features are a priority in the design of the GEN12AD-V. It includes automatic shut-off mechanisms that activate in the event of low oil pressure or overheating, protecting both the generator and connected devices. Furthermore, the generator is compliant with various safety standards, ensuring peace of mind for users.

The Ruud GEN12AD-V generator is an outstanding choice for those seeking a reliable, efficient, and durable power solution. Its blend of performance, technology, and safety features positions it as a leading option in the generator market, catering to the needs of both residential and commercial users. Whether for emergency backup power or recreational use, the GEN12AD-V delivers consistent performance and reliability.