Baldor GLC65, GLC60, GLC105, GLC45, GLC20, GLC30, GLC100, GLC15 manual ‐17 Generator Protect Setpoints

Page 49

 

Table 4‐17 Generator Protect Setpoints

 

 

 

 

 

Overload

 

Threshold for generator overload (in % of Nominal power)

 

 

Step: 1% of Nominal power; Range: 0 - 200%

 

 

 

 

 

Overload Wrn

 

Threshold for generator overload warning (in % of Nominal power)

 

 

Step: 1% of Nominal power; Range: 0 - 200%

 

 

 

 

 

Overload del

 

Delay for generator overload alarm. Step: 0.1s; Range: 0 - 60.0 s

Ishort

 

Shutdown occurs when short circuit limit Ishort limit is reached.

 

 

Step: 1 % of Nominal current; Range: 100 - 500 %

 

 

 

 

 

2Inom del

 

IDMT curve shape selection. 2Inom del is Reaction time of IDMT

 

 

protection for 200% overcurrent Igen = 2* Nominal current.

 

 

Step: 0,1 s; Range: 0,1 - 20 s

 

 

IDMT is “very inverse” generator over current protection. Reaction time is

 

 

not constant but depends on generator over current level according

 

 

following formula. Reaction time is limited up to 900 sec = 15 minutes.

 

 

IDMT protection is not active for Reaction time values longer than 15

 

 

minutes.

 

 

2lnomdel * Nomincurrent

 

 

ReactionTime +

 

 

 

lgen * Nomincurrent

Curr unbal

 

Threshold for generator current asymmetry (unbalance).

 

 

Step: 1% of Nominal current; Range: 1 - 100% of Nominal current

 

 

 

Curr unbal del

 

Delay for generator current assymetry. Step: 0.1 s; Range: 0 - 60.0 s

Gen >V

 

Shutdown level for generator overvoltage. All three phases are checked.

 

 

Maximum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: Gen >V Wrn -200%

 

 

 

Gen >V Wrn

 

Warning level for generator overvoltage. All three phases are checked.

 

 

Maximum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: Gen <V Wrn - Gen >V

 

 

 

Gen <V Wrn

 

Warning level for generator under voltage. All three phases are checked.

 

 

Minimum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: Gen <V - Gen >V Wrn

 

 

 

Gen <V

 

Shutdown level for generator under voltage. All three phases are checked.

 

 

Minimum out of three is used.

 

 

Step: 1% of Nominal voltage; Range: 0% - Gen <V Wrn

 

 

 

Gen V del

 

Delay for generator under voltage and over voltage alarm

 

 

Step: 0.1s; Range: 0 - 60 s

 

 

 

Volt unbal

 

Threshold for generator voltage unbalance alarm.

 

 

Step: 1% of Nominal voltage; Range: 0 - 100% of Nominal voltage

 

 

 

Volt unbal del

 

Delay for generator voltage unbalance alarm.

 

 

Step: 0.1s; Range: 0 - 60.0 s

 

 

 

Gen >f

 

Shutdown level for generator over frequency.

 

 

Step: 0.1% of Nominal frequency; Range: Gen > Wrn - 200.0%

 

 

 

Gen >f Wrn

 

Warning level for generator over frequency.

 

 

Step: 0.1% of Nominal frequency; Range: Gen <f Wrn - Gen >V

 

 

 

Gen <f

 

Shutdown level for generator under frequency.

 

 

Step: 0.1% of Nominal frequency; Range: 0.0 - Gen <f Wrn

 

 

 

Gen <f Wrn

 

Warning level for generator under frequency.

 

 

Step: 0.1% of Nominal frequency; Range: Gen <f - Gen >f Wrn

 

 

 

Gen f del

 

Delay for generator under frequency and over frequency alarm.

 

 

Step: 0.1s; Range: 0 - 60.0 s

 

 

 

 

 

MN2408

Operation 4‐9

Image 49
Contents MN2408 GLC GeneratorCalifornia Proposition 65 Warning Table of Contents Appendix a Troubleshooting and Maintenance Problems and SolutionsAppendix B Read This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Battery Safety Maintenance Warranty Period Limited WarrantyAny warranty coverage Generator Series Labor Parts‐2 General Information MN2408 Site Planning Installation GuidelinesEngine Cooling System Controls and Transfer SwitchExhaust System Room AirSetting The Genset On An Existing Concrete Floor Slab Foundation Design Foundation ChecklistVibration Isolators ‐2 Approximate Weight vs. kW Output Weight Of The Genset‐3 Calculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationSoil Type Safe Bearing Capacity Lb per ft Kilo Pascals ‐5 Typical Foundation InstallationExhaust System ‐6 Exhaust System Calculations Exhaust Piping Transfer Switch Checklist Transfer SwitchTransfer Switch Location Battery Location Battery Starting SystemBattery Cables Battery Charger‐14 General Information MN2408 ‐1 Generator Lifting When the Generator is installed outdoors‐3 Stub Up Detail ‐2 Mounting DimensionsGenerator Open SoundVentilation Test Secure the GeneratorBackpressure must not exceed 20 of water column Hot Exhaust GassesGuidelines for Exhaust System Page ‐4 Fuel Consumption Natural and LPV Fuel ConnectionsGeneral Considerations Example Determining Pipe Size for Natural Gas External Supply Piping by installerNatural Gas Connections Pipe Iron Pipe Size Length‐6 LP Vapor Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPVCatalog No Rating Single Phase Power Connections Transfer Switch ConsiderationsRemote Start Neutral L1L2 Connections AC Power Connections GroundConnections General Wiring Considerations Battery Charger ConsiderationsGLC10-25 Recommended Engine Oil and Battery TypeGLC100 GLC125Post Installation Checks Post Installation Checks ‐16 Receiving & Installation MN2408 Digital Engine Controller Description EM0046A21 MRS17 ‐8 Alarm & Warning ConditionsMAN Mode OFF ModeAUT Mode Digital Engine Controller Description EM0046A21 MRS17Alarm List Adjustment MenuECU Alarm List Menu Status Condition of Transition Action  Next StateSensor fail FLS see ‐10 AlarmsShut down SD see ‐10 ‐10 Possible Warnings‐11 Binary Inputs Inputs and Outputs‐12 Binary outputs Used for shunt trip‐13 Analog Inputs Set points‐14 Basic Setpoints ‐15 Engine Setpoints ‐15 Engine Setpoints Delay for Analog Input 2 Wrn Wtemp low. s Range1-180 s‐16 Engine Protect Setpoints During the first 500ms. ,1s Range 0 3s‐17 Generator Protect Setpoints ‐19 IOM/PTM Module Setpoints ‐18 Sensor Spec Setpoints‐11 Controller Connection Diagram Jdic Speed Signal LED Alarm LEDRun Switch OFF SwitchManual Start/Stop Operator Control PanelAutomatic Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownUtility Power Restored Utility Power Failure ConditionsUtility Normal Condition Load Test Push-button OperationDigital Input Faults Internal FaultsFault Digital Inputs Name Action Terminal # No Load Test‐15 Engine Controller Inputs & Outputs Fault Inputs Name Action Signal Analog FaultsCrank Such as Fuel Rack Solenoids or electronic governorsEngine starter motor Fail Programmable ContactsAction Description Display Comments Reset faults Apply Power Main LCD DisplayShow Operating Status screens Name and remaining timeGenerator Phase/Neutral Voltage Display Line to Neutral Generator Phase Voltage Display Line to LineGenerator Phase Current Display Generator Average Output DisplayProgram Menus Navigation Hints Main Menu Loop Zero Calibration Voltage Calibration ProcedureSpan Calibration Repeat for each phaseDisplayed values Displays the type of calibration function Engine Temperature & Oil Pressure CalibrationOil Pressure ‐16 Configuration Data Sheet System Voltage Line To Line Parameter Setting Range120-15000V AC Toggle Between Psi/KpaParameter Setting ‐21 Engine Control Connections ‐34 Operation MN2408 Engine General‐1 General Troubleshooting Guide Problems and SolutionsProblem Possible Cause Remedy ‐2 Troubleshooting Guide Digital Controller Only Service ‐3 Troubleshooting Guide Analog Controller OnlyVerify the adjustments. Replace controller if failed Installation Considerations Battery ChargerBattery Options & Accessories A‐1Figure A‐2 Battery Heating Pad Installation BTHTR81 Heater Engine Block Heater Options & Accessories A‐3GLC10-25 GLC30-45 GLC60-90 GLC100-105 SilencersFuel Strainers & Fuel Lines Options & Accessories A‐5Fuel Strainer Stop Figure A‐6 InstallationRemote Annuciators Options & Accessories A‐7Generator Radiator Duct FlangeGLC30-60 GLC80-100Enclosures Options & Accessories A‐9GLC10-25 H1=36.0 L1=11.75 GLC30-45 H1=52.1, H2=66.6 GLC60-90 H1=64.2, H2=76.8‐10 Series GLC MN2408 GLC Circuit Breaker & Electrical Data Qty per PhaseOSH Plant Series GLC B‐1Figure B‐11 Customer Interface Connection Diagram Series GLC B‐3 Figure B‐13 Single Phase w/o Breaker Connection Diagram Series GLC B‐5 Figure B‐14 Single Phase One Breaker Connection DiagramFigure B‐15 Single Phase Two Breaker Connection Diagram Series GLC B‐7 ‐8 Series GLC MN2408 Series GLC B‐9 ‐10 Series GLC MN2408 Series GLC B‐11 Figure B‐20 Three Phase Connection DiagramFigure B‐21 Three Phase Connection Diagram with PMG Series GLC B‐13 ‐14 Series GLC MN2408 Series GLC B‐15 ‐16 Series GLC MN2408 Series GLC B‐17 Figure B‐27 Control Box Connections with MEC20 Controller Series GLC B‐19 Figure B‐29 Control Box Connections with MEC2 Controller Series GLC B‐21 Figure B‐30 Engine Wiring, Woodward 4.3L GMFigure B‐31 Engine Wiring, Woodward 5.7L GM Series GLC B‐23 Figure B‐32 Engine Wiring, Woodward 8.1L GM‐24 Series GLC MN2408 Baldor District Offices Baldor Electric Company MN2408