Battery Charger

An engine mounted alternator charges the batteries during engine operation. Standby gensets should include a solid state battery charger that is connected to utility power so the battery is charged continuously while the genset is not running. The battery charger should be connected to the utility power emergency circuit. The batteries on prime power gensets are charged by the engine mounted alternator, if equipped.

The output of the battery charger or the belt driven alternator must be connected directly to the battery or to the battery terminals on the starter to prevent the electronic governor from acting erratically. Make control connections to the genset control using a conduit with a flexible section at the genset to avoid damage due to genset vibrations.

Battery Cables

The wire size (wire gauge) of the cables connecting the starter to the batteries must be large enough to ensure proper voltage at the engine starter motor during cranking. The total cranking circuit resistance includes the resistance of the cables from the starting motor to the battery and the resistance of all relays, solenoids, switches, and connections. The resistance of various sizes of cables is shown in Figure 2‐10. For purposes of calculating cranking circuit resistance to select cable size, the resistance of each connection can be taken as .00001 ohms and the resistance of each relay, solenoid, and switch can be taken as .0002 ohms. Figure 2‐10 illustrates an example of a typical cranking circuit resistance calculation.

Figure 2‐10 Typical Battery Cable Calculations

MN2408

General Information 2‐13

Image 23
Contents MN2408 GLC GeneratorCalifornia Proposition 65 Warning Table of Contents Appendix B Troubleshooting and Maintenance Problems and SolutionsAppendix a Read This Manual Thoroughly Section Product Safety InformationOperation SymbolsOperation Warning Statements Burn Installation Battery Safety Maintenance Generator Series Labor Parts Limited WarrantyWarranty Period Any warranty coverage‐2 General Information MN2408 Site Planning Installation GuidelinesRoom Air Controls and Transfer SwitchEngine Cooling System Exhaust SystemVibration Isolators Foundation Design Foundation ChecklistSetting The Genset On An Existing Concrete Floor Slab ‐2 Approximate Weight vs. kW Output Weight Of The Genset‐3 Calculate Soil Bearing Load SBL Capacity Designing An Isolated FoundationSoil Type Safe Bearing Capacity Lb per ft Kilo Pascals ‐5 Typical Foundation InstallationExhaust System ‐6 Exhaust System Calculations Exhaust Piping Transfer Switch Location Transfer SwitchTransfer Switch Checklist Battery Location Battery Starting SystemBattery Cables Battery Charger‐14 General Information MN2408 ‐1 Generator Lifting When the Generator is installed outdoorsSound ‐2 Mounting Dimensions‐3 Stub Up Detail Generator OpenVentilation Test Secure the GeneratorGuidelines for Exhaust System Hot Exhaust GassesBackpressure must not exceed 20 of water column Page General Considerations Fuel Connections‐4 Fuel Consumption Natural and LPV Pipe Iron Pipe Size Length External Supply Piping by installerExample Determining Pipe Size for Natural Gas Natural Gas Connections‐6 LP Vapor Flow Rate Cubic Feet per Hour per Pipe Length Example Determining Pipe Size for LPVCatalog No Rating Remote Start Transfer Switch ConsiderationsSingle Phase Power Connections Connections AC Power Connections GroundNeutral L1L2 Connections General Wiring Considerations Battery Charger ConsiderationsGLC125 Recommended Engine Oil and Battery TypeGLC10-25 GLC100Post Installation Checks Post Installation Checks ‐16 Receiving & Installation MN2408 Digital Engine Controller Description EM0046A21 MRS17 ‐8 Alarm & Warning ConditionsDigital Engine Controller Description EM0046A21 MRS17 OFF ModeMAN Mode AUT ModeMenu Status Condition of Transition Action  Next State Adjustment MenuAlarm List ECU Alarm List‐10 Possible Warnings AlarmsSensor fail FLS see ‐10 Shut down SD see ‐10Used for shunt trip Inputs and Outputs‐11 Binary Inputs ‐12 Binary outputs‐14 Basic Setpoints Set points‐13 Analog Inputs ‐15 Engine Setpoints During the first 500ms. ,1s Range 0 3s Delay for Analog Input 2 Wrn Wtemp low. s Range1-180 s‐15 Engine Setpoints ‐16 Engine Protect Setpoints‐17 Generator Protect Setpoints ‐19 IOM/PTM Module Setpoints ‐18 Sensor Spec Setpoints‐11 Controller Connection Diagram Jdic OFF Switch Alarm LEDSpeed Signal LED Run SwitchAutomatic Start/Stop Operator Control PanelManual Start/Stop Automatic Mains Failure AMF Automatic Fault ShutdownLoad Test Push-button Operation Utility Power Failure ConditionsUtility Power Restored Utility Normal ConditionNo Load Test Internal FaultsDigital Input Faults Fault Digital Inputs Name Action Terminal #‐15 Engine Controller Inputs & Outputs Fault Inputs Name Action Signal Analog FaultsFail Programmable Contacts Such as Fuel Rack Solenoids or electronic governorsCrank Engine starter motorAction Description Display Comments Name and remaining time Apply Power Main LCD DisplayReset faults Show Operating Status screensGenerator Average Output Display Generator Phase Voltage Display Line to LineGenerator Phase/Neutral Voltage Display Line to Neutral Generator Phase Current DisplayProgram Menus Navigation Hints Main Menu Loop Zero Calibration Voltage Calibration ProcedureDisplayed values Repeat for each phaseSpan Calibration Oil Pressure Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function ‐16 Configuration Data Sheet Toggle Between Psi/Kpa Parameter Setting RangeSystem Voltage Line To Line 120-15000V ACParameter Setting ‐21 Engine Control Connections ‐34 Operation MN2408 Engine GeneralProblem Possible Cause Remedy Problems and Solutions‐1 General Troubleshooting Guide ‐2 Troubleshooting Guide Digital Controller Only Verify the adjustments. Replace controller if failed ‐3 Troubleshooting Guide Analog Controller OnlyService Options & Accessories A‐1 Battery ChargerInstallation Considerations BatteryFigure A‐2 Battery Heating Pad Installation BTHTR81 Heater Engine Block Heater Options & Accessories A‐3GLC10-25 GLC30-45 GLC60-90 GLC100-105 SilencersFuel Strainer Options & Accessories A‐5Fuel Strainers & Fuel Lines Stop Figure A‐6 InstallationRemote Annuciators Options & Accessories A‐7GLC80-100 Radiator Duct FlangeGenerator GLC30-60GLC60-90 H1=64.2, H2=76.8 Options & Accessories A‐9Enclosures GLC10-25 H1=36.0 L1=11.75 GLC30-45 H1=52.1, H2=66.6‐10 Series GLC MN2408 Series GLC B‐1 Qty per PhaseGLC Circuit Breaker & Electrical Data OSH PlantFigure B‐11 Customer Interface Connection Diagram Series GLC B‐3 Figure B‐13 Single Phase w/o Breaker Connection Diagram Series GLC B‐5 Figure B‐14 Single Phase One Breaker Connection DiagramFigure B‐15 Single Phase Two Breaker Connection Diagram Series GLC B‐7 ‐8 Series GLC MN2408 Series GLC B‐9 ‐10 Series GLC MN2408 Series GLC B‐11 Figure B‐20 Three Phase Connection DiagramFigure B‐21 Three Phase Connection Diagram with PMG Series GLC B‐13 ‐14 Series GLC MN2408 Series GLC B‐15 ‐16 Series GLC MN2408 Series GLC B‐17 Figure B‐27 Control Box Connections with MEC20 Controller Series GLC B‐19 Figure B‐29 Control Box Connections with MEC2 Controller Series GLC B‐21 Figure B‐30 Engine Wiring, Woodward 4.3L GMFigure B‐31 Engine Wiring, Woodward 5.7L GM Series GLC B‐23 Figure B‐32 Engine Wiring, Woodward 8.1L GM‐24 Series GLC MN2408 Baldor District Offices Baldor Electric Company MN2408