Baldor GLC105, GLC60, GLC45, GLC20, GLC65 Span Calibration, Displayed values, Repeat for each phase

Page 68

Span Calibration

Energize the generator supply voltage to the controller at nominal level. Note: It may be necessary to program the

 

optional under and over voltage shutdowns as alarms to ensure the generator will continue to operate during calibration.

 

Caution must be taken to ensure the generator output voltage is set within nominal limits. In the programming mode,

 

scroll to the desired generator supply voltage phases with the SPAN function selected. Connect an external AC voltmeter

 

of adequate voltage range and accuracy to the controller terminals associated with the voltage phases to be calibrated.

 

Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while observing the

 

displayed voltage level. Adjust the correction factor number to obtain an identical voltage reading as measured with the

 

external AC voltmeter. With the correct voltage displayed, press the ENTER push-button to accept the correction factor

 

number. Record the correction factor number on the programming sheet for future reference.

Note:

When the span calibration setting is complete, re-confirm the zero calibration points. If the zero calibration setpoint needs

 

further adjustment, the span calibration point must also be re-calibrated.

Current Sensing Calibration To accurately calibrate the current sensors, an external test AC ammeter and current clamp is required, with an accuracy of 0.5% or better.

 

 

CURRENT A ZERO

 

 

 

99

350A

 

 

 

 

 

 

Displays the generator load current (phase A, B or C) to be calibrated.

 

Displays the type of calibration function, either ZERO or SPAN.

 

Displays the calibration correction factor number (0-255) used to obtain the correct current reading.

 

Note: To correctly calibrate any of the current sensors, the ZERO function must be calibrated before the SPAN function.

 

Displays the actual current measurement that will be the same value as shown on the MEC 2 display menus for

 

generator supply. This current reading may be calibrated higher or lower by changing the correction factor number.

Zero Calibration

Connect an external AC ammeter with current clamp of adequate current range to the controller terminals associated with

 

the current phases to be calibrated. With the generator stopped, confirm there is “0” current on the phases to be

 

calibrated. In the programming mode, scroll to each of the desired generator supply current phases with the ZERO

 

function selected. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while

 

observing the displayed current level. Adjust the correction factor until “0” amps is displayed.

 

With the correct current displayed, press the ENTER push-button to accept the correction factor number. Record the

 

correction factor number on the programming sheet for future reference. Repeat for each phase.

Span Calibration

Apply 50%-100% load to the generator set. It is recommended to load the generator set to 100% rated load for

 

calibration purposes to obtain good accuracy throughout the full span of operation. Do not exceed the current rating of

 

the CT. Non-linear output of the CT will result when the secondary current exceeds 5 amps and will similarly effect the

 

displayed values.

 

 

 

In the programming mode, scroll to the desired generator supply current phases with the SPAN function selected.

 

Connect an external AC ammeter and current clamp of adequate current range to the controller terminals associated with

 

the current phases to be calibrated. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor

 

number while observing the displayed current value. Adjust the correction factor number to obtain an identical current

 

reading as measured with the external AC ammeter. With the correct current displayed, press the ENTER push-button to

 

accept the correction factor number. Record the correction factor number on the programming sheet for future reference.

 

Repeat for each phase.

 

 

Note:

When the span calibration setting is complete, re-confirm the zero calibration points. If the zero calibration setpoint needs

 

further adjustment, the span calibration point must also be re-calibrated.

Battery Voltage Calibration To accurately calibrate the MEC 2 battery voltage sensor, an external test DC voltmeter is required, with an accuracy of 0.5% or better.

BAT VOLTS SPAN

99 24.6V

Displays the type of calibration function (SPAN).

Displays the calibration correction factor number (0-255) used to obtain the correct voltage reading.

Displays the actual battery voltage measurement that will be the same value as shown on the MEC 2 display menu. This voltage reading may be calibrated higher or lower by changing the correction factor.

SPAN Calibration Energize the battery supply voltage to the controller and connect the external test DC voltmeter to the battery terminals, B+ and B-. In the programming mode, scroll to the battery span calibration point. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while observing the displayed battery voltage level on the MEC 2. Adjust the correction factor number to obtain an identical voltage reading as measured with the external DC voltmeter. With the correct voltage displayed, press the ENTER push-button to accept the correction factor number. Record the correction factor number on the programming sheet for future reference.

4‐28 Operation

MN2408

Image 68
Contents GLC Generator MN2408California Proposition 65 Warning Table of Contents Appendix B Troubleshooting and Maintenance Problems and SolutionsAppendix a Section Product Safety Information Read This Manual ThoroughlySymbols OperationOperation Warning Statements Burn Installation Battery Safety Maintenance Limited Warranty Warranty PeriodAny warranty coverage Generator Series Labor Parts‐2 General Information MN2408 Installation Guidelines Site PlanningControls and Transfer Switch Engine Cooling SystemExhaust System Room AirVibration Isolators Foundation Design Foundation ChecklistSetting The Genset On An Existing Concrete Floor Slab Weight Of The Genset ‐2 Approximate Weight vs. kW OutputDesigning An Isolated Foundation ‐3 Calculate Soil Bearing Load SBL Capacity‐5 Typical Foundation Installation Soil Type Safe Bearing Capacity Lb per ft Kilo PascalsExhaust System ‐6 Exhaust System Calculations Exhaust Piping Transfer Switch Location Transfer SwitchTransfer Switch Checklist Battery Starting System Battery LocationBattery Charger Battery Cables‐14 General Information MN2408 When the Generator is installed outdoors ‐1 Generator Lifting‐2 Mounting Dimensions ‐3 Stub Up DetailGenerator Open SoundSecure the Generator Ventilation TestGuidelines for Exhaust System Hot Exhaust GassesBackpressure must not exceed 20 of water column Page General Considerations Fuel Connections‐4 Fuel Consumption Natural and LPV External Supply Piping by installer Example Determining Pipe Size for Natural GasNatural Gas Connections Pipe Iron Pipe Size LengthExample Determining Pipe Size for LPV ‐6 LP Vapor Flow Rate Cubic Feet per Hour per Pipe LengthCatalog No Rating Remote Start Transfer Switch ConsiderationsSingle Phase Power Connections Connections AC Power Connections GroundNeutral L1L2 Connections Battery Charger Considerations General Wiring ConsiderationsRecommended Engine Oil and Battery Type GLC10-25GLC100 GLC125Post Installation Checks Post Installation Checks ‐16 Receiving & Installation MN2408 ‐8 Alarm & Warning Conditions Digital Engine Controller Description EM0046A21 MRS17OFF Mode MAN ModeAUT Mode Digital Engine Controller Description EM0046A21 MRS17Adjustment Menu Alarm ListECU Alarm List Menu Status Condition of Transition Action  Next StateAlarms Sensor fail FLS see ‐10Shut down SD see ‐10 ‐10 Possible WarningsInputs and Outputs ‐11 Binary Inputs‐12 Binary outputs Used for shunt trip‐14 Basic Setpoints Set points‐13 Analog Inputs ‐15 Engine Setpoints Delay for Analog Input 2 Wrn Wtemp low. s Range1-180 s ‐15 Engine Setpoints‐16 Engine Protect Setpoints During the first 500ms. ,1s Range 0 3s‐17 Generator Protect Setpoints ‐18 Sensor Spec Setpoints ‐19 IOM/PTM Module Setpoints‐11 Controller Connection Diagram Jdic Alarm LED Speed Signal LEDRun Switch OFF SwitchAutomatic Start/Stop Operator Control PanelManual Start/Stop Automatic Fault Shutdown Automatic Mains Failure AMFUtility Power Failure Conditions Utility Power RestoredUtility Normal Condition Load Test Push-button OperationInternal Faults Digital Input FaultsFault Digital Inputs Name Action Terminal # No Load Test‐15 Engine Controller Inputs & Outputs Analog Faults Fault Inputs Name Action SignalSuch as Fuel Rack Solenoids or electronic governors CrankEngine starter motor Fail Programmable ContactsAction Description Display Comments Apply Power Main LCD Display Reset faultsShow Operating Status screens Name and remaining timeGenerator Phase Voltage Display Line to Line Generator Phase/Neutral Voltage Display Line to NeutralGenerator Phase Current Display Generator Average Output DisplayProgram Menus Navigation Hints Main Menu Loop Voltage Calibration Procedure Zero CalibrationDisplayed values Repeat for each phaseSpan Calibration Oil Pressure Engine Temperature & Oil Pressure CalibrationDisplays the type of calibration function ‐16 Configuration Data Sheet Parameter Setting Range System Voltage Line To Line120-15000V AC Toggle Between Psi/KpaParameter Setting ‐21 Engine Control Connections ‐34 Operation MN2408 General EngineProblem Possible Cause Remedy Problems and Solutions‐1 General Troubleshooting Guide ‐2 Troubleshooting Guide Digital Controller Only Verify the adjustments. Replace controller if failed ‐3 Troubleshooting Guide Analog Controller OnlyService Battery Charger Installation ConsiderationsBattery Options & Accessories A‐1Figure A‐2 Battery Heating Pad Installation BTHTR81 Heater Options & Accessories A‐3 Engine Block HeaterSilencers GLC10-25 GLC30-45 GLC60-90 GLC100-105Fuel Strainer Options & Accessories A‐5Fuel Strainers & Fuel Lines Figure A‐6 Installation StopOptions & Accessories A‐7 Remote AnnuciatorsRadiator Duct Flange GeneratorGLC30-60 GLC80-100Options & Accessories A‐9 EnclosuresGLC10-25 H1=36.0 L1=11.75 GLC30-45 H1=52.1, H2=66.6 GLC60-90 H1=64.2, H2=76.8‐10 Series GLC MN2408 Qty per Phase GLC Circuit Breaker & Electrical DataOSH Plant Series GLC B‐1Figure B‐11 Customer Interface Connection Diagram Series GLC B‐3 Figure B‐13 Single Phase w/o Breaker Connection Diagram Figure B‐14 Single Phase One Breaker Connection Diagram Series GLC B‐5Figure B‐15 Single Phase Two Breaker Connection Diagram Series GLC B‐7 ‐8 Series GLC MN2408 Series GLC B‐9 ‐10 Series GLC MN2408 Figure B‐20 Three Phase Connection Diagram Series GLC B‐11Figure B‐21 Three Phase Connection Diagram with PMG Series GLC B‐13 ‐14 Series GLC MN2408 Series GLC B‐15 ‐16 Series GLC MN2408 Series GLC B‐17 Figure B‐27 Control Box Connections with MEC20 Controller Series GLC B‐19 Figure B‐29 Control Box Connections with MEC2 Controller Figure B‐30 Engine Wiring, Woodward 4.3L GM Series GLC B‐21Figure B‐31 Engine Wiring, Woodward 5.7L GM Figure B‐32 Engine Wiring, Woodward 8.1L GM Series GLC B‐23‐24 Series GLC MN2408 Baldor District Offices Baldor Electric Company MN2408