Vapor x High Limit
The LP gas vapor temperature sensor located in the gas pipe train downstream from the vaporizer, has opened indicating that the vaporizor is running too hot and must be readjusted. This sensor is set at 200°F (93°C) and automatically resets itself when cool. The message will distinguish between which burner caused the shutdown. The reference to the number one (1) is telling you that it is burner number 1 which is the bottom most fan/heater unit, is where the malfunction is located.
Try adjusting the vaporizer coils farther away from the burners flame. You may also want to try switching the burner mode from Hi/Lo to On/Off, especially on warmer days.
INPUT/OUTPUT GENERATED ERRORS
The following is a list of errors that are generated with the Input/Output board located in the upper control box.
Air System Failure
A shutdown has occurred due to a air system that was installed with an intergal safety switch that was in the unit. The air system safety connections are located in the upper control box on the terminal strip. This can occur if this safety looses 12VDC to terminal
Aux Load Overload
The motor overload relay has tripped on the Aux Load Motor circuit located in the upper control box. This can occur if this safety looses 12VDC to terminal
Aux Unload Overload
The motor overload relay has tripped on the Aux Unload Motor circuit located in the upper control box. This can occur if this safety looses 12VDC to terminal