Unload Motor Overload
The motor overload has tripped on the Unload Motor Overload located in the upper control box. This indicates that 12VDC has been lost to terminal
User Safety
A shutdown has occurred due to a user installed safety switch that was installed on the dryer. The user installed safety connections are located in the upper control box on the terminal strip. This also indicates that 12VDC has been lost to terminal
MASTER DISPLAY GENERATED ERRORS
The following is a list of errors that are generated with the Master Display board located in the lower control box.
Cont-Batch Mode Chng
This error occurs when you switch the dryer mode switch from the Cont. Flow to the Staged Batch position while the dryer is running in the Continous Flow Mode. To avoid this shutdown, stop the dryer before switching modes. Press Stop to clear the error.
Network Failed FH x
This error is generated whenever Fan/Heater board has lost its communications link with the Input/Output board (upper control panel door) and the Master Display board (lower control panel). Check the blue and yellow wires marked
| 55 |