Warning

Maintenance may only be performed by a qualified service and maintenance engineer.

Table 10.2 Displayed errors (Sheet 4 of 10)

is

Code + Description

Possible cause

Solution

Remark

 

 

 

 

 

F03 (lock out error)

Damaged wiring /

1.

Check the wiring between the pressure switch and the

If the error cannot be resolved or is persistent, contact your

The pressure switch

Open circuit

 

controller.

installer.

 

 

 

To replace the necessary parts, you must contact your installer.

fails to work correctly.

 

2.

If necessary, replace the wiring.

 

 

 

 

 

 

Pressure switch not

1.

Check the running speed of the fan. See ’8.7.4 Displaying

 

 

closing.

 

appliance specifications’.

 

 

 

2.

Check that the hoses on the pressure switch and the air supply

 

 

 

 

hose between fan and burner are correctly fitted. Refit these if

 

 

 

 

necessary.

 

 

 

3.

Check the hoses on the pressure switch and the air supply

 

 

 

 

hose between fan and burner for cracks. If necessary, replace

 

 

 

 

the hoses.

 

 

 

4.

Check whether the flue gas discharge is compliant with

 

 

 

 

Table 3.7.

 

 

 

5.

Check for blockage in the flue gas discharge. Remove any

 

 

 

 

blockage that may be present.

 

 

 

6.

Check for blockage in the condensation water discharge.

 

 

 

 

Remove any blockage that may be present.

 

 

 

7.

Measure the pressure differential across the pressure switch.

 

 

 

 

See Table 12.1. If there is insufficient pressure differential,

 

 

 

 

clean the heat exchanger. If the pressure differential is

 

 

 

 

acceptable, check that the pressure switch is closing, using a

 

 

 

 

multimeter.

 

 

 

 

 

 