Warning

Maintenance may only be performed by a qualified service and maintenance engineer.

Table 10.2 Displayed errors (Sheet 7 of 10)

is

Code + Description

Possible cause

 

Solution

 

Remark

 

 

 

 

 

 

 

F09 (lock out error)

Temperature at the top

 

1.

Check that the circulation pump (if present) is working.

 

If the error cannot be resolved or is persistent, contact your

Water temperature

of the tank exceeds

 

2.

Check the position of the temperature sensor T1.

 

installer.

93°C.

 

 

 

protection.

 

3.

Reset the water heater controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n Remark

 

 

 

 

 

 

Error “F09” remains active in the event that the water

 

 

 

 

 

 

temperature during a reset was higher than 78 oC. If this is the

 

 

 

 

 

 

case, first draw water off by opening the nearest hot water tap,

 

 

 

 

 

 

so that cold water can flow in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F10 (lock out error)

Pressure switch not

 

1.

Check the running speed of the fan. See ’8.7.4 Displaying

 

If the error cannot be resolved or is persistent, contact your

Restriction on number

closing.

 

 

appliance specifications’.

 

installer.

 

 

2.

Check that the hoses on the pressure switch and the air supply

 

To replace the necessary parts, you must contact your installer.

of ignition attempts

 

 

 

 

 

 

 

based on pressure

 

 

 

hose between fan and burner are correctly fitted. Refit these if

 

 

switch state changes.

 

 

 

necessary.

 

 

 

 

 

3.

Check for cracks in the hoses on the pressure switch and the

 

 

 

 

 

 

air supply hose between fan and burner. If necessary, replace

 

 

 

 

 

 

the hoses.

 

 

 

 

 

4.

Check whether the flue gas discharge is compliant with

 

 

 

 

 

 

Table 3.8.

 

 

 

 

 

5.

Check for blockage in the flue gas discharge. Remove any

 

 

 

 

 

 

blockage that may be present.

 

 

 

 

 

6.

Check for blockage in the condensation water discharge.

 

 

 

 

 

 

Remove any blockage that may be present.

 

 

 

 

 

7.

Measure the pressure differential across the pressure switch.

 

 

 

 

 

 

Table 12.1. If there is insufficient pressure differential, clean the

 

 

 

 

 

 

heat exchanger. If the pressure differential is acceptable, check

 

 

 

 

 

 

that the pressure switch is closing, using a multimeter.

 

 

 

 

 

8.

 

 

 

 

 

 

 

 

 

 

Release R.1.3 UK

79

Page 79
Image 79
A.O. Smith 28 30 50 60 service manual Error F09 remains active in the event that the water, F10 lock out error